background image

7

Siemens Ltd.

Product development is a continuous process. Consequently 
the data indicated in this Leaflet is subject to change without 
prior notice. For latest issue contact our sales offices.

SACHIN ENTERPRISE

Disposal

Siemens product are environment friendly, which predominantly 
consist of recyclable materials.
For disposals we recommend disassembling and separation into 
following materials:
METALS: Segregate into Ferrous & Non Ferrous types for recycling 
through authorised dealer.

PLASTICS: Segregate as per material type for recycling through 
authorised dealer. Because of the long lifetime of Siemens 
products the disposal guidelines may be replaced by other national 
regulations when taking the product out of service.
The local customer care service is available at any time to answer 
disposal-related questions

Customer Care Toll free no. 1800 209 0987 

Email: [email protected] 

Order No. A5E40846135A

a) Manual switching (MANL) :

DI :

b) Rotational switching (ROTN) :

c) Automatic switching (AUTO) :

d) Linear switching (LINR) :

1) When this switching program is selected, the capacitor steps are controlled manually by the user.

2)

When user selects manual switching through Auto / Manual switch on the panel, then all the relays that are 'ON' through APFC are turned 'OFF' and

then user can manually turn every capacitor bank through push button available on panel for respective banks. In this case APFC has no more control and
it switches off all bank that it was earlier controlling.

This switching program is based on rotational first-in-first-out sequence. This option will automatically switch in and out

the capacitors according to the targeted power factor, sensitivity setting and the re-connection time setting.

This automatic switching program uses intelligent switching sequence. The step switching sequence is not fixed and the

program automatically selects the most appropriate steps to switch in or out in order to achieve shortest reaction time with minimum number of steps.

In this switching sequence it works in last in first out mode. This option will automatically switch in and out the capacitors

according to the targeted power factor, sensitivity setting and the re-connection time setting.

User Guide

Sensor Clip Assembly

Assemble sensor on the panel /Din rail clamp by using center screw provision
and M4 nut. As shown in below diagram.

1. PANEL MOUNTING ASSEMBLY :

2. DIN RAIL MOUNTING ASSEMBLY :

+

+

+

Phase-angle Setting

L3-N

L3-N

L3-N

L3

L1

L2

L2-N

L2-N

L2-N

L2

L3

L1

L1-N

L1-N

L1-N

L1

L2

L3

0

0

240

0

240

0

240

0

120

0

120

0

120

0

0

0

0

0

Voltage

CT

Phase-Angle

Voltage

CT

Phase-Angle

L1-L2

L1-L2

L1-L2

L3

L1

L2

L3-L1

L3-L1

L3-L1

L2

L3

L1

L2-L3

L2-L3

L2-L3

L1

L2

L3

90

0

90

0

90

0

330

0

330

0

330

0

210

0

210

0

210

0

Dimensional Drawing (mm)

Panel Cutout

(in mm)

138

138

Outline Dimensions (in mm)

144

136.5

14

4

5

50

Side
view

Front bezel

Mounting APFC:

Cable and Cover termination:

Security Information:

 In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement

– and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens products and solutions constitute one element
of such a concept. For more information about industrial security, please visit http://www.siemens.com/industrialsecurity.

/

AB

Summary of Contents for 7UG0571-1FT20

Page 1: ...e 50 to 440 VAC L L 30 to 250 VAC L N AC Network 3Φ 4W 3Φ 3W 2Φ 2W 1Φ 2W Display parameters Power Factor True RMS voltage Current Frequency Power KW KVA KVAr Energy KWh KVAh Temperature Control Supply 90 to 250 VAC 50 60Hz Power consumption 15VA Frequency range 50 60Hz Operating temperature 0 C to 60 C Humidity upto 95 without moisture condensation Alarm mode relay output Over voltage Under voltag...

Page 2: ...col Communication address Transmission Mode Data types Transmission distance Transmission speed Parity Stop bits RS AND 485 MODBUS RTU 1 to 255 Half duplex Float and Integer 500 Meter maximum 300 600 1200 2400 4800 9600 19200 in bps None Odd Even 1 or 2 7UG057 L N V I R C NO RS485 T1 T2 0 5 Nm 0 4 Nm 5 Solid 1 x 0 75 to 2 5 mm2 2 x 0 5 to 2 x 1 5 mm2 0 5 mm2 5 Stranded with end sleeve 1 x 0 5 to 2...

Page 3: ...phase Displays current of 1st phase Displays THD of current of 1st phase Press key 1st time Displays active power of 1st phase Displays reactive power of 1st phase Displays apparent power of 1st phase Press key 3rd time Press key 2nd time Displays active energy of 1st phase Displays reactive energy of 1st phase Displays apparent energy of 1st phase Displays temperature OK OK OK Parameter Key Key P...

Page 4: ...Trip Time No Yes Under Voltage Set No Yes Harmonics Range No Yes No Yes Over Voltage Set Step Error Step Error Setting CT Polarity Error Over Temperature Hysteresis Voltage Hysteresis PF Factory Default Yes No Temperature Range Setting Fan Setting Reset kVAh Reset Energy Password Correct Reset kWh No Yes Yes No Reset kVArh Bank 1 Bank 2 Bank 5 Bank 6 Bank 7 Bank 3 Bank 13 Bank 14 Bank 4 Bank 8 Ban...

Page 5: ... customer wants to reset energy 5min 5min Inst 5min 5min NA Inst 5min 2 5min 1min Inst 1min 1min NA Inst 50 240V L N 85 415 L L ON OFF 50 277V L N 85 480 L L ON OFF ON OFF ON OFF ON OFF 20 to 80 ON OFF 0 100 ON OFF ON OFF 1 to 10 1 to 5 20 100 50 YES NO YES NO YES NO YES NO YES NO 0001 9999 ON OFF Name of Parameter No Voltage Release Trip time setting TRIP TIME Over Voltage Nomenclature Default Va...

Page 6: ...02 CT Secondary A 1 100 100 1 9999 500 500000 1 255 1 5 Integer Integer 1 0x0000 0x0001 1 2 40010 1 0x0000 0x0001 0x0002 None Odd Even 40009 0x09 0x0A Parity Stop bit 0x0005 0x0006 9600 19200 Meaning Value Integer 1 0x0000 300 40008 0x08 Baud rate bps 0x0001 600 0x0002 1200 0x0003 2400 0x0004 4800 Formula to find address of individual Harmonic Note For Error 0 No Error 1 Error Present Meaning Cons...

Page 7: ...irst out sequence This option will automatically switch in and out the capacitors according to the targeted power factor sensitivity setting and the re connection time setting This automatic switching program uses intelligent switching sequence The step switching sequence is not fixed and the program automatically selects the most appropriate steps to switch in or out in order to achieve shortest ...