Chapter 3 - 7SR45 Performance Specification
©2018 Siemens Protection Devices Limited
Chapter 3 Page 10 of 14
Type Test
Reference
Parameters
Declared Operation
RV = 48 V DC
40 % RV for 0.2 s
Normal Operation
2
70 % RV for 0.5 s
Normal Operation
2
Gradual shutdown /
Start-up test
IEC 60255-26
Shut down ramp 60 s
Power off 5 mins
Start up ramp 60 s
Normal Operation
2
Voltage interruption
(AC/DC auxiliary
supply)
RV = 48 V/220 V DC
RV = 230 V AC
IEC 60255-26
0 % RV at 5 s
Normal Operation
2
Alternating
component in DC
(Ripple)
DC Power supply
IEC 60255-26
15 % of DC voltage
Normal Operation
1
1
No effect on relay performance
2
Restart with no mal-operation, loss of data or relay damage
RV = Residual Voltage
Table 1-15
Climatic Environmental Tests
Type Test
Reference
Requirement
Ambient Operating
Temperature
IEC 60068-2-1,
IEC 60068-2-2,
IEC 60255-1
-10
°
C to + 60
°
C
Permissible Temporary
Operating Temperature,
(Tested for 16 h) *
IEC 60068-2-1,
IEC 60068-2-2,
IEC 60255-1
-40
°
C
LCD display operating range: -20
°
C to + 70
°
C
Permissible Temporary
Operating Temperature,
(Tested for 96 h)
IEC 60068-2-1,
IEC 60068-2-2
IEC 60255-1
-20
°
C to + 70
°
C
Storage Temperature
(Non-operational) #
IEC 60068-2-1,
IEC 60068-2-2
IEC 60255-1
-25
°
C to + 70
°
C
Cold test operational
(Energized condition)
Cold test storage
(Unenergized
condition)
IEC 60068-2-1
IEC 60255-1
-10
°
C, 96 h
-25
°
C, 16 h
Dry heat test
operational
(Energized condition)
Dry heat test storage
(Unenergized condition)
IEC 60068-2-2
IEC 60255-1
+60
°
C, 96 h
+70
°
C, 16 h
Damp heat test, Steady
State
IEC 60068-2-78
IEC 60255-1
10 days at 93
±
3 % RH, +40
°
C
Damp heat test, Cyclic IEC 60068-2-30
IEC 60255-1
+25
…
55
°
C, R.H. > 93 % RH (6 cycles)
At lower temperature, 97 %, -2 % +3 % RH
At upper temperature, 93 %,
± 3
% RH