7SG13 Delta P20064 FM1 Autoreclosing 

2.1.5  In/Out Switching 

 

The DAR feature may be switched out by changing the A/R In Service setting by a number of methods. These are 
either a keypad change from the front panel, or via a communication, or by an A/R OUT status input. A/R OUT 
status input has priority over A/R IN. If both are raised the function will be in Out Of Service. Once the relay has 
been switched to Out Of Service the reverse action A/R IN is required before the function will go back to In 
Service. 

2.1.6  Overall Control 

 

The DAR feature may be disabled by a Lockout command or by an external signal applied to a status input (A/R 
OUT).  

If the Lockout command or A/R OUT are received while a DAR operation is in progress, the feature is immediately 
locked-out. An External A/R IN command can be received via a status input. This will re-enable the module.  

If the Lockout command is received while a Manual Close operation is in progress, the feature is immediately 
locked-out.  

The DAR or Manual Close feature may be paused by an external Block signal applied to a status input. This 
causes the feature to temporarily halt before it issues the next CB close command and can be used, for example, 
to delay CB closure until the CB pressure has reached an acceptable level. If the Block signal has not been 
removed before the end of a defined time, the Reclose Block Delay, the relay is locked-out.  

A Block Reclose input active within the deadtime resets the deadtime timer. 

2.1.7  CB Close Command pulse 

The duration of the CB Close Command pulse is settable to allow a range of CBs to be used. The Close pulse will 
be terminated if any protection Starter picks-up or a trip occurs. This is to prevent Close and Trip Command 
pulses existing simultaneously. A Close Onto Fault Output is given if a starter or trip picks-up in the Close Pulse. 
This can be independently wired to Lockout. 

2.1.8  CB Failed To Open and CB Failed to Close 

CB Failed To Open and CB Failed to Close features are used to confirm that a CB has not responded correctly to 
each Trip and Close Command. If a CB fails to operate, the DAR feature can be set to lockout. 

2.1.9  CB Closed by Another Device 

If, during a dead time period, the Relay detects that the CB has closed (due to an external source) it increments 
its Reclose count and advances to the next part of the Reclose sequence (begin Reclaim time). 

2.1.10 Indications 

The relay has a fully programmable output to either output contacts or LEDs, see settings sheet for complete list.  

The following are included: 
1. A/R 

Switched Out 

2.  A/R In Progress 
3. Successful 

Close 

4. Line 

Check 

5.  Ext Arc Start 
6. Lockout 
7.  CB Failed to Open 
8.  CB Failed to Close 

2.1.11 Trip and Reclose 

This is a test function, allowing the operation of the CB to be verified.  

The Trip signal should be routed directly to the Circuit Breaker. Once the CB has opened and the Trip and 
Reclose input is removed the DAR will wait for the first Reclose Delay and then issue a CB Close command.  

A Trip and Reclose command will only be accepted if the Relay is in quiescent, or line healthy mode, i.e. no 
autoreclose sequences are in progress. 

During the Trip and Reclose reclosure, Line Check is invoked to ensure that the CB does not repeatedly close 
onto a faulty line. 

©2010 Siemens Protection Devices Ltd. 

 

P20064 Page 5 of 7 

Summary of Contents for 7SG13 Delta

Page 1: ...e be reproduced from this document unless Siemens Protection Devices Ltd consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence or any other cause Any and all such liability is disclaimed 2010 Siemens Protection Device...

Page 2: ... 4 2 1 4 Manual Close 4 2 1 5 In Out Switching 5 2 1 6 Overall Control 5 2 1 7 CB Close Command pulse 5 2 1 8 CB Failed To Open and CB Failed to Close 5 2 1 9 CB Closed by Another Device 5 2 1 10 Indications 5 2 1 11 Trip and Reclose 5 2 1 12 Metering 6 2 1 13 Dead time and Reclaim Timing 6 2 1 14 Lockout 6 List of Figures Figure 1 1 Key to Functional Block Diagrams 3 2010 Siemens Protection Devic...

Page 3: ...start trip Elem Starter Elem Inhibit Elem Reset Delay c Forward Reverse Elem Char Dir Non Dir PhA Dir Blk PhaseAFwd Digital input signal status input visible to user Digital output signal output relay visible to user Digital signal not visible to user to from another element Setting block showing list of setting values with setting name Appropriate block is TRUE when setting selected other blocks ...

Page 4: ... for each of the 4 recloses 2 1 1 Protection Trip The protection element which trips the CB is used to prime and start the autoreclose sequence Internal protection elements that will start the A R are pre selected within the relay 2 1 2 Protection Starter If during a sequence the breaker is closed from another device and a fault is still on the system the starter element will be energised This is ...

Page 5: ...table to allow a range of CBs to be used The Close pulse will be terminated if any protection Starter picks up or a trip occurs This is to prevent Close and Trip Command pulses existing simultaneously A Close Onto Fault Output is given if a starter or trip picks up in the Close Pulse This can be independently wired to Lockout 2 1 8 CB Failed To Open and CB Failed to Close CB Failed To Open and CB ...

Page 6: ...he Reclose Block Delay due to a persistent Block signal not cleared At the end of the Sync Close Delay due to Synchronism not being achieved Once the Lockout condition has been reached it will be maintained until reset The following will reset lockout By a Manual Close command from fascia comms or a status input By a Reset Lockout signal provided there is no signal present that will cause Lockout ...

Page 7: ... Inputs A R In A R Out Extern A R Start Block Reclose Go To Lockout Trip And Reclose Trip and Lockout Reset Lockout Manual Close _ 1 for each status input 2 1 14 1 Specification Element Parameters The element will take the following parameters unless otherwise specified in the appropriate Diagrams and Parameters document Parameter Value tcycle Element cycle time 20 ms tsetting Timer settings Appli...