1.18
Test and calibration
WARNING!
The following measures must be carried out in compliance with the
accident prevention instructions. The appropriate electrical tools must be
used.
A calibration instrument, which indicates voltages, currents, and
phase angles with an error
≤
0.1 %, is required for testing the
transducer. The output signals are measured with a digital
multimeter of the same accuracy.
If a readjustment shall be carried out, a PC with the program
"SIMEAS PAR", like for the calibration, is required in addition to
the calibration instrument.
During calibration of the DC-current-outputs the burden must not
exceed a maximum output burden of R
BIN
=
7 5
, V
IAN
.