Connecting up
5.1 Safety when connecting up
SCALANCE S615
Operating Instructions, 10/2022, C79000-G8976-C389-07
49
WARNING
Improper installation of shielded cables
There is a risk of explosion due to equalizing currents between the hazardous area and the
non-hazardous area.
•
Ground shielded cables that cross hazardous areas at one end only.
•
Lay a potential equalization conductor when grounding at both ends.
WARNING
Insufficient isolation of intrinsically safe and non-intrinsically safe circuits
Risk of explosion in hazardous areas
•
When connecting intrinsically safe and non-intrinsically safe circuits, ensure that the
galvanic isolation is performed properly in compliance with local regulations (e.g. IEC
60079-14).
•
Observe the device approvals applicable for your country.
Notes for use in hazardous locations according to ATEX, IECEx, UKEX and CCC Ex
If you use the device under ATEX, IECEx, UKEX or CCC Ex conditions you must also keep to the
following safety instructions in addition to the general safety instructions for protection
against explosion:
WARNING
Transient overvoltages
Take measures to prevent transient overvoltages of more than 40% of the rated voltage (or
more than 119 V). This is the case if you only operate devices with SELV (safety extra-low
voltage).
WARNING
Suitable cables at high ambient temperatures in hazardous area
At an ambient temperature of ≥ 60 °C, use heat
-resistant cables designed for an ambient
temperature at least 20 °C higher. The cable entries used on the enclosure must comply
with the IP degree of protection required by EN IEC / IEC 60079-0, GB 3836.1.
General notes on use in hazardous areas according to UL-HazLoc
If you use the device under UL-HazLoc conditions, you must also adhere to the following
safety notices in addition to the general safety notices for protection against explosion: