background image

Summary of Contents for 6ES7142-6BG00-0BB0

Page 1: ......

Page 2: ... 0 5A M12 L 8xM12 6ES7142 6BG00 0BB0 Equipment Manual 07 2020 A5E46570894 AA Preface ET 200eco PN M12 L Documentation Guide 1 Product overview 2 Wiring 3 Parameters address space 4 Interrupts diagnostics alarms 5 Technical specifications 6 Dimension drawing A ...

Page 3: ...by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens product...

Page 4: ...stems machines and networks against cyber threats it is necessary to implement and continuously maintain a holistic state of the art industrial security concept Siemens products and solutions constitute one element of such a concept Customers are responsible for preventing unauthorized access to their plants systems machines and networks Such systems machines and components should only be connecte...

Page 5: ...controls and display elements 11 3 Wiring 12 3 1 Terminal and block diagram 12 3 2 Pin assignment 14 4 Parameters address space 18 4 1 Parameters 18 4 2 Explanation of the parameters 19 4 3 Address space 20 5 Interrupts diagnostics alarms 24 5 1 Status and error displays 24 5 2 Interrupts 27 5 3 Alarms 28 5 3 1 Diagnostics alarms 28 5 3 2 Maintenance events 29 6 Technical specifications 30 A Dimen...

Page 6: ...ATIC ET 200eco PN M12 L distributed I O system The STEP 7 online help supports you in the configuration and programming Device information Product manuals contain a compact description of the module specific information such as properties interfaces wiring diagrams display and operator control elements and technical specifications General information The function manuals contain detailed descripti...

Page 7: ... My ww en Application examples The application examples support you with various tools and examples for solving your automation tasks Solutions are shown in interplay with multiple components in the system separated from the focus on individual products You will find the application examples on the Internet https support industry siemens com sc ww en sc 2054 TIA Selection Tool With the TIA Selecti...

Page 8: ...he PG PC time converted to UTC time to the module Program download to CPU RUN STOP mode switchover CPU localization by means of LED flashing Reading out of CPU error information Reading the CPU diagnostics buffer Reset to factory settings Firmware update of the CPU and connected modules You can find the SIMATIC Automation Tool on the Internet https support industry siemens com cs ww en view 981613...

Page 9: ...optimally and to plan reserves This helps to prevent problems in commissioning or failures during productive operation even in advance of a planned operation This increases the availability of the production plant and helps improve operational safety The advantages at a glance Network optimization thanks to port specific calculation of the network load Increased production availability thanks to o...

Page 10: ...4VDC 0 5A M12 L 8xM12 6ES7142 6BG00 0BB0 Equipment Manual 07 2020 A5E46570894 AA 9 Product overview 2 2 1 Properties Article number 6ES7142 6BG00 0BB0 View of the I O device Figure 2 1 View of the I O device DQ 8x24VDC 0 5A M12 L 8xM12 ...

Page 11: ...e Suitable for solenoid valves DC contactors and indicator lights Dimensions 45 x 200 mm The I O device supports the following functions Firmware update Identification and maintenance data I M0 to I M3 Isochronous mode Value status Quality Information Module internal Shared Output MSO Shared Device Accessories The following components are included in the I O device package Identification labels Ot...

Page 12: ...he DQ 8x24VDC 0 5A M12 L 8xM12 I O device PN MF LAN Sockets for connecting PROFINET RN NS RUN network status LED ER MS ERROR module status LED MT IO MAINT IO status LED PWR Power LED for load voltage 2L P1 LK P2 LK LINK port status LEDs LED displays 0 to 7 for channel status channel error X10 to X17 Sockets for the output signal X80 Connector for infeed of supply and load voltage X81 Socket for lo...

Page 13: ...0 5A M12 L 8xM12 6ES7142 6BG00 0BB0 12 Equipment Manual 07 2020 A5E46570894 AA Wiring 3 3 1 Terminal and block diagram The figure below shows an example of the pin assignment of signal outputs with single and dual assignment of the sockets ...

Page 14: ...l assignment of the socket DQn Output signal Output single assignment of socket RN NS RUN network status LED green Output single assignment of socket ER MS ERROR module status LED red X10 to X17 Channels 0 to 7 MT IO MAINT IO status LED yellow X80 Infeed of supply and load voltage P1 LK LINK port 1 LED green X81 Loop through of supply and load voltage P2 LK LINK port 2 LED green X1 P1R PROFINET in...

Page 15: ...lowing table shows the pin assignment of the PROFINET connector Table 3 1 Pin assignment of the PROFINET connector port 1 and 2 Pin Assignment of the core color of the PROFINET cable Assignment Front view of the connectors Assignment X1 P1R 1 Yellow TXP 2 White RXP 3 Orange TXN 4 Blue RXN Thread Functional earth FE Assignment X1 P2R 1 Yellow RXP 2 White TXP 3 Orange RXN 4 Blue TXN Thread Functiona...

Page 16: ... DQ7 Connector X17 Not assigned 3 Ground 2M 4 Connector X10 Output signal DQ0 Connector X11 Output signal DQ1 Connector X12 Output signal DQ2 Connector X13 Output signal DQ3 Connector X14 Output signal DQ4 Connector X15 Output signal DQ5 Connector X16 Output signal DQ6 Connector X17 Output signal DQ7 5 Functional earth FE Note the assignment of the output signals to the respective sockets in the f...

Page 17: ... or single assignment of sockets Pin assignment of the connector for infeed of the supply voltage M12 L coded The table below shows the pin assignment of the M12 L coded connector for infeed of the supply voltage Table 3 3 Pin assignment of the supply voltage connector Pin Assignment of the core color of the power cable Assignment Front view of the connector X80 connector POWER input 1 Brown Suppl...

Page 18: ...M12 L coded The table below shows the pin assignment of the M12 L coded socket for loop through of the supply voltage Table 3 4 Pin assignment of the supply voltage socket Pin Assignment of the core color of the power cable Assignment Front view of the socket X81 socket POWER output 1 Brown Supply voltage 1L non switched 2 White Ground 2M switched 3 Blue Ground 1M non switched 4 Black Load voltage...

Page 19: ... Configurable parameters and their defaults GSD file Parameters Value range Default Scope with configu ration software e g STEP 7 TIA Portal Diagnostics Undervoltage 1L Disable Enable Disable Channel Diagnostics Missing 2L Disable Enable Disable Channel Diagnostics Short circuit Disable Enable Disable Channel Diagnostics Wire break Disable Enable Disable Channel Reaction to CPU STOP Shutdown Keep ...

Page 20: ...ents Page 29 Diagnostics Missing 2L Enabling of the diagnostics for missing or insufficient load voltage 2L Diagnostics Short circuit Enabling of the diagnostics for short circuit of the output to ground Diagnostics Wire break Enabling of diagnostics when the line between the actuator and the I O device is interrupted Reaction to CPU STOP With this parameter you set the reaction of the digital out...

Page 21: ... options Configuration Short designation device name in the GSD file device view in the configuration software Configuration software e g with STEP 7 TIA Portal Integrated in hardware catalog STEP 7 TIA Portal GSD file in STEP 7 TIA Portal V11 or higher or STEP 7 V5 5 SP4 HF1 or higher 1 x 8 channel DQ 8x24VDC DQ 8x24VDC V16 or higher with HSP 0299 X 1 x 8 channel DQ 8x24VDC QI DQ 8x24VDC QI V16 o...

Page 22: ...x 8 channel DQ 8x24VDC QI The following figure shows the address space allocation for the configuration as 8 channel I O device digital outputs with value status Figure 4 2 Address space for configuration as 1 x 8 channel DQ 8x24VDC QI with value status Address space for configuration as 1 x 8 channel DQ 8x24VDC MSO With the configuration 1 x 8 channel I O device module internal shared output MSO ...

Page 23: ...n error is pending at the channel and that the value is faulty For the 2nd Submodule MSO submodule the value status 0 indicates The value is faulty The basic submodule is not yet assigned parameters not ready The connection between the IO controller and the basic submodule has been interrupted The IO controller of the basic submodule is in STOP or POWER OFF state The following figure shows the ass...

Page 24: ...ce assignment for configuration as a 2 x 4 channel I O device digital outputs The start addresses of the two submodules can be assigned freely Figure 4 4 Address space for configuration as 2 x 4 channel DQ 8x24VDC S Reference You can find information on the functionality Module internal Shared Input Shared Output MSI MSO in the STEP 7 online help or in the function manual SIMATIC PROFINET with STE...

Page 25: ...splays The figure below shows the LED displays status and error displays of the I O device DQ 8x24VDC 0 5A M12 L 8xM12 RN NS RUN network status LED green ER MS ERROR module status LED red MT IO MAINT IO status LED yellow PWR Power LED for load voltage 2L green P1 LK P2 LK LINK port status LEDs green LED displays 0 to 7 for channel status channel error green red Figure 5 1 LED displays ...

Page 26: ...oximately 0 25 s The three LEDs light up simultaneous ly for approximately 2 s while Reset to factory settings is running Flash ing Off Off The ET 200eco PN is disabled Activate the ET 200eco PN with the configuration software or via the user program The ET 200eco PN is not or incorrectly configured Configure the ET 200eco PN via the configuration software The ET 200eco PN is starting up The ET 20...

Page 27: ...Status display of the PWR LED PWR LED Meaning Off Load voltage 2L is missing or too low On Load voltage 2L present P1 LK and P2 LK LEDs Table 5 3 Error display of the P1 LK and P2 LK LEDs LEDs Meaning Solution P1 LK P2 LK Off There is no Ethernet connection between the communications interface of your IO device and a communication partner e g IO controller Check whether the bus cable to the switch...

Page 28: ...el sta tus channel error Off Process value 0 On Process value 1 On Channel diagnostics 5 2 Interrupts The I O device digital outputs DQ 8x24VDC 0 5A M12 L 8xM12 supports diagnostic interrupts and maintenance alarms Diagnostic interrupt The I O device generates a diagnostic interrupt on the following events Wire break Internal module fault 2L missing or too low Short circuit to ground Maintenance a...

Page 29: ...able 5 5 Diagnostics alarms their meanings and corrective measures Diagnostics alarm Error code Meaning Corrective measures Wire break 6H Fault in the external circuitry Check the external circuitry and correct the fault Actuator faulty Replace the actuator Actuator circuit impedance too high Use a different actuator type or modify the wiring For example use cables with a larger cross section Inte...

Page 30: ...ial problems as soon as possible The I O device signals a maintenance event to the higher level diagnostic system on the following event Table 5 6 Triggering of a maintenance event Maintenance alarm Error code Event Meaning Maintenance demanded MT IO LED is lit 2H Undervoltage Supply voltage 1L is below the tolerance limit System alarms in STEP 7 The maintenance information is generated in STEP 7 ...

Page 31: ...ware version V1 0 x FW update possible Yes Vendor identification VendorID 002AH Device identifier DeviceID 0306H Product function I M data Yes I M0 to I M3 Isochronous mode Yes Prioritized startup Yes Engineering with STEP 7 TIA Portal configurable integrated from version STEP 7 V16 or higher with HSP 0299 PROFINET from GSD version GSD revision GSDML V2 3 x Operating mode DQ Yes MSO Yes Supply vol...

Page 32: ...utputs Number of digital outputs 8 Current sourcing Yes Short circuit protection Yes per channel electronic Response threshold typ 1 A Limitation of inductive shutdown voltage to Typ 2L 52 V Controlling a digital input Yes Switching capacity of the outputs with resistive load max 0 5 A with inductive load max 0 5 A on lamp load max 5 W Load resistance range lower limit 48 Ω upper limit 4 kΩ Output...

Page 33: ...f PROFINET interfaces 1 1 Interface Interface type PROFINET with 100 Mbit s full duplex 100BASE TX Interface types Number of ports 2 integrated switch Yes M12 port Yes 2x M12 4 pin D coded Protocols PROFINET IO Device Yes Open IE communication Yes Interface types M12 port Autonegotiation Yes Autocrossing Yes Transmission rate max 100 Mbit s Protocols Supports protocol for PROFINET IO Yes PROFINET ...

Page 34: ...able Yes Monitoring the supply voltage Yes parameterizable Yes Wire break Yes Short circuit Yes Outputs to M channel by channel Diagnostics indication LED RUN LED Yes green LED ERROR LED Yes red LED MAINT LED Yes Yellow LED Channel status display Yes green LED for channel diagnostics Yes red LED For load voltage monitoring Yes green LED Connection display LINK TX RX Yes green LED only link Potenti...

Page 35: ...t temperature during operation min 40 C max 60 C Altitude during operation relating to sea level Ambient air temperature barometric pres sure altitude Up to max 5 000 m at installation height 2 000 m additional restrictions Connection method Design of electrical connection for the inputs and outputs M12 5 pin A coded Design of electrical connection for supply volt age M12 4 pin L coded Dimensions ...

Page 36: ...7142 6BG00 0BB0 Equipment Manual 07 2020 A5E46570894 AA 35 Dimension drawing A A 1 Dimension drawing The figure below shows the dimension drawing of the I O device digital outputs DQ 8x24VDC 0 5A M12 L 8xM12 in front and side views Figure A 1 Dimension drawing ...

Reviews: