Parameters/address space
4.2 Explanation of the parameters
I/O device digital outputs DQ 8x24VDC/0.5A M12-L 8xM12 (6ES7142-6BG00-0BB0)
Equipment Manual, 07/2020, A5E46570894-AA
19
4.2
Explanation of the parameters
Diagnostics: Undervoltage 1L+
Enabling of diagnostics for insufficient supply voltage 1L+.
Diagnostics: Undervoltage 1L+ triggers the "Undervoltage" maintenance event. You can find
more information in section Maintenance events (Page 29).
Diagnostics: Missing 2L+
Enabling of the diagnostics for missing or insufficient load voltage 2L+.
Diagnostics: Short-circuit
Enabling of the diagnostics for short-circuit of the output to ground.
Diagnostics: Wire break
Enabling of diagnostics when the line between the actuator and the I/O device is interrupted.
Reaction to CPU STOP
With this parameter, you set the reaction of the digital outputs of the I/O device after a CPU
STOP:
•
Shutdown: The digital output is de-energized.
•
Keep last value: The last value of the digital output remains activated.
•
Output substitute value 1: The I/O device outputs the substitute value "1".