Ambient conditions
SITOP PSU8200 3ph
44
Manual, 11.2014, C98130-A7638-A1-2-7629
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V / 40 A)
Damaging gases
Tested according to:
•
EN 60068-2-42 sulfur dioxide
•
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure
Operation:
•
1080 ... 795 hPa (-1000 ...+2000 m)
•
For operation at altitudes of 2000 m up to 6000 m above sea level: output must be
derated by -7.5 % / 1000 m or the ambient temperature must be reduced by
5 K / 1000 m (see Figure 4-3 Mounting height derating (Page 20)
•
Overvoltage category:
III to 2000 m (EN 50178)
II from 2000 m to 6000 m (EN 50178)
II to 2000 m (EN 60950-1)
I from 2000 m to 6000 m (EN 60950-1)
Storage:
•
1080 ... 660 hPa (-1000 ...+3500 m)