Technical data
6.2 Output
SITOP PSU8200 3ph
30
Manual, 11.2014, C98130-A7638-A1-2-7629
Figure 6-1
Power failure buffering
6.2
Output
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V / 40 A)
Output
Regulated, isolated DC voltage
Regulated, isolated DC voltage
Rated voltage value Ua rated DC
24 V
24 V
Total tolerance, static ±
3 %
3 %
Static line regulation, approx.
0,1 %
0,1 %
Static load regulation, approx.
0,2 %
0,2 %
Residual ripple in the load range
Peak-peak, max.
100 mV
100 mV
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
200 mV
200 mV
Adjustment range
24 … 28.8 V
24 … 28.8 V
Product function / output voltage can
be adjusted
Yes
Yes
Output voltage setting
•
Remark
Via potentiometer
Max. 480 W
Via potentiometer
Max. 960 W
Operating display
LED green for "24 V O.K."
LED green for "24 V O.K."
Signaling
Relay contact (NO contact, rating 60 V DC / 0.3 A) for "24 V O.K."
Response when switching on/off
No overshoot of Ua (soft start)
No overshoot of Ua (soft start)
Starting delay, max.
2.5 s
2.5 s
Voltage rise, typ.
150 ms
150 ms
Voltage rise time / of the output volt-
age / maximum
500 ms
500 ms
Rated current value Ia rated
20 A
40 A
Current range
•
Remark
0 … 20 A
+60 ...+70 °C derating: approx. 3 %
Ia rated/K
0 … 40 A
+60 .. +70 °C derating: approx. 4 %
Ia rated/K