SITOP PSU8200 3ph
Manual, 11.2014, C98130-A7638-A1-2-7629
29
Technical data
6
Note
Technical data is applicable for a rated input voltage, rated load and +25° C ambient
temperature (if nothing else is specified).
6.1
Input
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V / 40 A)
Input
3-phase, AC
3-phase, AC
Rated voltage value Ue rated
400-500 V
400-500 V
Voltage range
•
Remark
320 ... 575 V
Derating at Ue < 340 V: 10 % [Ia]
320 ... 575 V
Derating at Ue < 340 V: 10 % [Ia]
Wide-range input
Yes
Yes
Overvoltage strength
-
2.3 × Ue rated, 1.3 ms
Power failure buffering
at Ia rated, min
15 ms
15 ms
Rated line frequency
50-60 Hz
50-60 Hz
Line frequency range
47 ... 63 Hz
47 ... 63 Hz
Input current / at rated value of input
voltage 400 V
1.2 A
2.6 A
Input current / at rated value of input
voltage 500 V
1 A
2.1 A
Switch-on current limitation (+ 25 °C),
max.
18 A
56 A
I²t, max
0.8 A
2
s
2.24 A
2
s
Integrated input fuse
None
None
Protection in the line feeder cable
(IEC 898)
Required: 3-pole coupled miniature
circuit breaker (IEC 898) characteristic
C, 6 ... 16 A or 3RV2011-1DA10 circuit
breaker, (setting 3 A) or
3RV2711-1DD10 (UL 489)
Required: 3-pole coupled miniature
circuit breaker 10 ... 16 A characteris-
tic C or RV2011-1DA10 circuit breaker
(setting 3 A) or 3RV2711-1DD10
(UL 489)