November 15, 2006 

Mounting Plate Installation without an  
Existing Cutout 

Use one of the following methods: 

Using a drill

 or 

Using a metal-cutting saw

 for cutting the mounting 

hole depending on the tools available. 

Using a drill: 

1.  See Figure 8. Use this diagram to locate the 

holes from the 

corner of the case

. Do not use 

the corner of the mounting plate as the 
reference point. Mark the locations on the fume 
hood. 

2.  See Figure 4. Using the mounting plate as a 

template, mark the locations of the two mounting 
holes.  

3.  Drill the required holes using the locations and 

sizes shown in Figure 8. 

NOTE: 

If FLN or AUX connections are not 
required for installation, then only 
drill holes for the air tube and power. 

4.  Using a 1/8-inch (3.0 mm) bit, drill the two 

mounting holes. 

5.  Using the screws provided, attach the mounting 

plate to the mounting surface. 

Using a metal-cutting saw: 

1.  See Figure 9. Use this diagram to locate the 

rectangular cutout from the 

corner of the case

Do not use the corner of the mounting plate as 
the reference point. 

2.  Using the mounting plate as a template, mark 

the locations of the two mounting holes and the 
2 inch 

×

 3 inch (5.0 

×

 8.0 cm) cutout.  

See Figure 4. 

 

Figure 4.  Installation without an Existing Cutout. 

3.  Using a metal-cutting saw or other suitable tool, 

remove the marked rectangular area. 

4.  Using a 1/8-inch (3.0 mm) bit, drill the two 

mounting holes. 

5.  Using the screws provided, attach the mounting 

plate to the mounting surface. 

6. Proceed 

to 

Sidewall Hose Mounting

Sidewall Hose Mounting: 

NOTE: 

The location of the sidewall adapter greatly 
affects the performance of the Fume Hood 
Monitor. Use the 

FHM Hood Evaluation 

Kit

, part number 546-00320, to accurately 

determine the location for the sidewall 
adapter. 

1.  Mark the location of the hole for the air sensor 

hose 3 inches (7.5 cm) above the highest sash 
opening and 6 to 8 inches (15.0 to 20.0 cm) 
back from the sash track. 

NOTE: 

The hole location for the air sensor 
may vary slightly due to hood 
construction.

 

On fume hoods with a 

mechanical stop, 

do not 

use the 

mechanical stop as a reference 
point. Use the highest possible open 
position of the sash as the reference 
point. 

2.  At the mark found in step 1, drill a 1/2- inch  

(13.0 mm) hole in the sidewall of the fume hood. 

 

CAUTION: 

 

If the construction of the fume hood 
contains fiber-cement panels, then use 
diamond core drill bits to drill holes inside 
the fume hood. Fiber-cement panels are 
used for impact, moisture, and fire 
resistant applications. Diamond core drill 
bits are designed for hard and abrasive 
materials. Standard drill bits may crack and 
damage fiber-cement panels. 

Siemens Building Technologies, Inc.

  

Page 3 of 6

 

Summary of Contents for 546-00303A

Page 1: ...l flat blade screwdriver Small Philips screwdriver Wire strippers For a fume hood without an existing cutout Medium duty electric drill 1 8 inch 3 0 mm drill bit 1 2 inch 13 0 mm drill bit Metal cutting saw or 3 4 in and 1 in drill bits or hole saws Small flat blade screwdriver Small Philips screwdriver Wire strippers Expected Installation Time 27 minutes Prerequisites Power cable in place If usin...

Page 2: ... Existing Cutout Mounting Plate Installation with an Existing Cutout 1 See Figure 3 If the fume hood is provided with a 2 inch 4 inch 5 0 10 0 cm cutout with an electric utility box then use the provided machine screws to attach the mounting plate to the electric utility and skip to Sidewall Hole Mounting If the fume hood has no electric utility box make sure that the cutout provides enough cleara...

Page 3: ...n without an Existing Cutout 3 Using a metal cutting saw or other suitable tool remove the marked rectangular area 4 Using a 1 8 inch 3 0 mm bit drill the two mounting holes 5 Using the screws provided attach the mounting plate to the mounting surface 6 Proceed to Sidewall Hose Mounting Sidewall Hose Mounting NOTE The location of the sidewall adapter greatly affects the performance of the Fume Hoo...

Page 4: ...r sensor hose onto the end of the plastic sidewall adapter and insert the other end through the hole in the mounting plate Hose and Wire Connections 1 Insert the end of the air sensor hose onto the air sensor connection on the back of the FHM See Figure 6 Figure 7 Location of Wire Receptacles 6 If using the auxiliary DI s or an external alarm Use the wire strippers and remove 1 4 inch 6 35 mm of i...

Page 5: ...Document No 546 00310 Installations Instructions November 15 2006 Siemens Building Technologies Inc Page 5 of 6 Figure 8 Full Size Template Location of Holes for Using a Drill ...

Page 6: ...to make changes in specifications and models as design improvements are introduced 2000 Siemens Building Technologies Inc Siemens Building Technologies Inc Landis Staefa Division 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 U S A Document No 546 00310 Printed in the U S A Page 6 of 6 Figure 9 Full Size Template Location of Hole for Using a Metal Cutting Saw ...

Reviews: