Siemens 546-00303A Installation Instructions Manual Download Page 1

 

 

Installation Instructions

Document No. 546-00310 

November 15, 2006

 

Fume Hood Monitor 

 

 

 

Page 1 of 6 

Product Description 

The Fume Hood Monitor (FHM) (Figure 1) provides 
visual and audible alarms to alert a fume hood user 
of airflow conditions. The mounting plate is designed 
for fume hoods with or without existing cutouts. This 
kit contains: 

 

Fume Hood Monitor with mounting plate 

 

Three removable wire connectors 

 

Four sheet metal screws 

 

Two machine screws 

 

2 ft. (0.6 m) air sensor hose 

 

Plastic sidewall adapter and lock ring 

Product Numbers 

546-00303A Fume 

Hood 

Monitor 

546-00303B 

Fume Hood Monitor mounting plate 

Warning/Caution Notations 

CAUTION: 

 

 

Equipment damage or loss of 
data may occur if the user 
does not follow procedure as 
specified. 

Required Tools 

For a fume hood with an existing cutout: 

 

Medium-duty electric drill 

 

1/2-inch. (13.0 mm) drill bit 

 

Small flat-blade screwdriver 

 Small 

Philips 

screwdriver 

 Wire 

strippers 

For a fume hood without an existing cutout: 

 

Medium-duty electric drill 

 

1/8-inch (3.0 mm) drill bit  

 

1/2-inch (13.0 mm) drill bit  

 

Metal-cutting saw or 3/ 4 in. and 1 in. drill bits 
or hole saws 

 

Small flat-blade screwdriver 

 Small 

Philips 

screwdriver 

 Wire 

strippers 

Expected Installation Time 

27 minutes 

Prerequisites 

 

Power cable in place 

If using a field panel: 

 

Floor Level Network (FLN) cable from the 
field panel to the FHM in place 

If using an external alarm or auxiliary DI 
connection: 

 

External alarm or auxiliary DI cable from 
source to FHM in place 

 

Figure 1.  Fume Hood Monitor. 

Instructions 

NOTE: 

Mount the FHM so that the fume hood 
operator can easily read its display and 
can easily reach its buttons. This height is 
approximately 4-1/2 ft. to 5 ft.  
(1.4 to 1.5 m) from the floor. 

1.  Choose the mounting location for the FHM. The 

FHM should be mounted directly on the fume 
hood and can be mounted over a pre-existing 
cutout on the fume hood. See Figure 2 for 
installation clearance requirements. 

Summary of Contents for 546-00303A

Page 1: ...l flat blade screwdriver Small Philips screwdriver Wire strippers For a fume hood without an existing cutout Medium duty electric drill 1 8 inch 3 0 mm drill bit 1 2 inch 13 0 mm drill bit Metal cutting saw or 3 4 in and 1 in drill bits or hole saws Small flat blade screwdriver Small Philips screwdriver Wire strippers Expected Installation Time 27 minutes Prerequisites Power cable in place If usin...

Page 2: ... Existing Cutout Mounting Plate Installation with an Existing Cutout 1 See Figure 3 If the fume hood is provided with a 2 inch 4 inch 5 0 10 0 cm cutout with an electric utility box then use the provided machine screws to attach the mounting plate to the electric utility and skip to Sidewall Hole Mounting If the fume hood has no electric utility box make sure that the cutout provides enough cleara...

Page 3: ...n without an Existing Cutout 3 Using a metal cutting saw or other suitable tool remove the marked rectangular area 4 Using a 1 8 inch 3 0 mm bit drill the two mounting holes 5 Using the screws provided attach the mounting plate to the mounting surface 6 Proceed to Sidewall Hose Mounting Sidewall Hose Mounting NOTE The location of the sidewall adapter greatly affects the performance of the Fume Hoo...

Page 4: ...r sensor hose onto the end of the plastic sidewall adapter and insert the other end through the hole in the mounting plate Hose and Wire Connections 1 Insert the end of the air sensor hose onto the air sensor connection on the back of the FHM See Figure 6 Figure 7 Location of Wire Receptacles 6 If using the auxiliary DI s or an external alarm Use the wire strippers and remove 1 4 inch 6 35 mm of i...

Page 5: ...Document No 546 00310 Installations Instructions November 15 2006 Siemens Building Technologies Inc Page 5 of 6 Figure 8 Full Size Template Location of Holes for Using a Drill ...

Page 6: ...to make changes in specifications and models as design improvements are introduced 2000 Siemens Building Technologies Inc Siemens Building Technologies Inc Landis Staefa Division 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 U S A Document No 546 00310 Printed in the U S A Page 6 of 6 Figure 9 Full Size Template Location of Hole for Using a Metal Cutting Saw ...

Reviews: