Siemens 546-00303A Installation Instructions Manual Download Page 2

Document No. 546-00310 
Installations Instructions  
November 15, 2006 

 

Figure 2.  Installation Clearance Requirements. 

NOTE: 

Clearance is needed to prevent the sensor 
air hose from bending or kinking, and to 
insert the Portable Operator’s Terminal 
Cable. 

2.  Confirm that an earth ground is connected to the 

mounting plate. To do this, make sure that the 
following conditions are met: 

a.  The conduit junction box is grounded, or 

b.  The fume hood enclosure is grounded, or 

c.  A separate wire is connected between the 

earth ground and the mounting plate. 

3.  Continue with one of the following mounting 

methods:  

Mounting Plate Installation with an 

Existing Cutout

 or 

Mounting Plate Installation 

without an Existing Cutout

 

Mounting Plate Installation with an 
Existing Cutout 

1.  See Figure 3. If the fume hood is provided with a 

2 inch 

×

 4 inch (5.0 

×

 10.0 cm) cutout with an 

electric utility box, then use the provided 
machine screws to attach the mounting plate to 
the electric utility and skip to 

Sidewall Hole 

Mounting

If the fume hood has no electric utility box, 

make sure that the cutout provides enough 
clearance for the air sensor hose and to 
connect the power, FLN, external alarm, and 
auxiliary DI wires. Then continue to Step 2. 

 

Figure 3.  Installation with an Existing Cutout. 

2.  Position the bracket over the opening and mark 

the locations of the two mounting holes. 

3.  Using the 1/8-inch (3.0 mm) drill bit, drill the two 

mounting holes. 

4.  Using the screws provided, attach the mounting 

plate to the mounting surface. 

5. Proceed 

to 

Sidewall Hose Mounting

Page 2 of 6

 

Siemens Building Technologies, Inc. 

Summary of Contents for 546-00303A

Page 1: ...l flat blade screwdriver Small Philips screwdriver Wire strippers For a fume hood without an existing cutout Medium duty electric drill 1 8 inch 3 0 mm drill bit 1 2 inch 13 0 mm drill bit Metal cutting saw or 3 4 in and 1 in drill bits or hole saws Small flat blade screwdriver Small Philips screwdriver Wire strippers Expected Installation Time 27 minutes Prerequisites Power cable in place If usin...

Page 2: ... Existing Cutout Mounting Plate Installation with an Existing Cutout 1 See Figure 3 If the fume hood is provided with a 2 inch 4 inch 5 0 10 0 cm cutout with an electric utility box then use the provided machine screws to attach the mounting plate to the electric utility and skip to Sidewall Hole Mounting If the fume hood has no electric utility box make sure that the cutout provides enough cleara...

Page 3: ...n without an Existing Cutout 3 Using a metal cutting saw or other suitable tool remove the marked rectangular area 4 Using a 1 8 inch 3 0 mm bit drill the two mounting holes 5 Using the screws provided attach the mounting plate to the mounting surface 6 Proceed to Sidewall Hose Mounting Sidewall Hose Mounting NOTE The location of the sidewall adapter greatly affects the performance of the Fume Hoo...

Page 4: ...r sensor hose onto the end of the plastic sidewall adapter and insert the other end through the hole in the mounting plate Hose and Wire Connections 1 Insert the end of the air sensor hose onto the air sensor connection on the back of the FHM See Figure 6 Figure 7 Location of Wire Receptacles 6 If using the auxiliary DI s or an external alarm Use the wire strippers and remove 1 4 inch 6 35 mm of i...

Page 5: ...Document No 546 00310 Installations Instructions November 15 2006 Siemens Building Technologies Inc Page 5 of 6 Figure 8 Full Size Template Location of Holes for Using a Drill ...

Page 6: ...to make changes in specifications and models as design improvements are introduced 2000 Siemens Building Technologies Inc Siemens Building Technologies Inc Landis Staefa Division 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 U S A Document No 546 00310 Printed in the U S A Page 6 of 6 Figure 9 Full Size Template Location of Hole for Using a Metal Cutting Saw ...

Reviews: