Description
20
9229 0106 176 0-
2020-09-18
Technical data
*
)
Depending on ambient conditions and temperature
**)
29 kV for UL
Fig. 13
Electrical data
Fig. 14
Rated data of solenoid actuator
1-pole
3-pole
Electrical data
3TM
12
13
14
15
32
33
34
35
36
Rated voltage
U
r
(phase-to-phase)
kV
7.2
12
7.2
12
15
Rated voltage
U
r
(phase-to-earth)
kV
4.15
6.9
–
–
–
–
–
Rated frequency
f
r
Hz
50-60
Rated lightning impulse withstand voltage
Up
kV
60
75
60
75
75
Rated short-duration power frequency withstand volt-
age
U
d
kV
20
32
28
42
20
32
28**
)
/42
20
Rated operating current
I
e
(at ambient temperatures
ranging from -40 °C to +70 °C)
A
450
320
Thermal current
I
th
*
)
A
450
320
Rated inrush current
kA
4.5
3.2
Rated breaking current
kA
3.6
2.65
Rated short-circuit breaking current (limit switch capa-
bility)
kA
5
4.5
5
5
4.5
Rated short-circuit current (effective value) 1 s
kA
8
1-pole
3-pole
Solenoid actuator
3TM
12/13
14/15
32/33
34/35
36
Rated supply voltage
U
a
(-
15
% to +10
%)
V
24 V DC to 32 V DC
V
48 V DC to 60 V DC
V
110 V DC to 125 V DC / 100 V AC to 120 V AC
V
220 V DC to 250 V DC / 230 V AC to 240 V AC
Start-up power loss, maximum (for max. 1 ms per clos-
ing)
(VA)
1400
Start-up power loss
(VA)
700
Holding mode power loss
(VA)
10 to 20
Closing time
ms
55 ±15
Optional additional adjustable on-time delay
ms
50 ±10
Off-time (without latching mounted)
ms
75 ±10
40 ±10
Optional additional adjustable off-time delay
24 V DC to 60 V DC
ms
50 ±10
110 V DC to 250 V DC / 100 V AC to 240 V AC
ms
30 / 60 / 90 ± 10
Off-time (with electric tripping)
ms
35 ±10
35 ±10
Summary of Contents for 3TM
Page 12: ...Transport storage packaging 12 9229 0106 176 0 2020 09 18 Blank page ...
Page 26: ...Description 26 9229 0106 176 0 2020 09 18 Blank page ...
Page 36: ...Installation 36 9229 0106 176 0 2020 09 18 Blank page ...
Page 48: ...Maintenance 48 9229 0106 176 0 2020 09 18 Blank page ...
Page 50: ...Index 50 9229 0106 176 0 2020 09 18 Blank page ...