3UG4501 filling level monitoring relay
5.7 Technical data
3UG4 / 3RR2 monitoring relays
Manual, 05/2016, NEB927043002000/RS-AC/004
97
3UG4501-..A..
3UG4501-..W..
Electromagnetic compatibility
IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Operating current at 17 V minimum
mA
5
Continuous current of the DIAZED fuse
link of the output relay
A
4
Resistance against vibration according to
IEC 60068-2-6
1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
Shock resistance according to IEC 60068-
2-27
sinusoidal half-wave 15g / 11 ms
Installation altitude at a height over sea
level maximum
m
2 000
Current carrying capacity of output relay
•
at AC-15
–
at 250 V at 50/60 Hz
A
3
–
at 400 V at 50/60 Hz
A
3
•
at DC-13
–
at 24 V
A
1
–
at 125 V
A
0.2
–
at 250 V
A
0.1
Conductor-bound parasitic coupling BURST
according to IEC 61000-4-4
2 kV
Conductor-bound parasitic coupling
conductor-earth SURGE according to IEC
61000-4-5
2 kV
Conductor-bound parasitic coupling
conductor-conductor SURGE according to
IEC 61000-4-5
1 kV
Electrostatic discharge according to IEC
61000-4-2
6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling according to
IEC 61000-4-3
10 V/m
Insulation voltage for overvoltage category
III according to IEC 60664 with degree of
pollution 3 rated value
V
300
Degree of pollution
3
Apparent power consumed
•
at 24 V for AC maximum
V·A
2
•
at 240 V for AC maximum
V·A
—
4
Ambient temperature
•
during operating
°C
-25 … +60
•
during storage
°C
-40 … +80
•
during transport
°C
-40 … +80