3UG4641 cos phi and active current monitoring relay
11.3 Functions
3UG4 / 3RR2 monitoring relays
292
Manual, 05/2016, NEB927043002000/RS-AC/004
Startup delay
To be able to start a drive, the output relay switches to the correct state during the ON-delay
time (onDel) depending on the selected open-circuit principle or closed-circuit principle, even
if the measured value is still under the set value.
Tripping delay
If the measured value overshoots or undershoots the set threshold after expiry of the ON-
delay time (onDel), the set tripping delay time (Del) and the relay symbol will flash. After
expiry of this time, the output relays change the switching state. On the display, the current
measuring value and the symbol for undershoot or overshoot flash.
You will find the switching states of the output relays below in section "Function diagrams"
and in Chapter "Diagnostics (Page 297)."