Installation
3PCI SCR Power Controller Series Manual
2-2
s
Version 1.2 (19000325)
Wiring rated at 75°C is required for all 3PCI model current ratings.
The 3PCI is phase-rotation insensitive. That is, three-phase input power can be connected in any
sequence to terminals
L1
,
L2
, and
L3
, and will not cause an out-of-phase condition.
Warning!
Branch circuit overcurrent protection required is to be provided in accordance with the
national and local codes of the inspecting authority.
AC Input
Load
3
2
1
3
2
1
Figure 2-1. Typical 3PCI Line and Load Connections
Table 2-1. Wire Size Information
Current Rating
Smallest Allowable
Conductor Size
Largest Allowable
Conductor Size
60, 90 and 120 A
8 AWG
0 AWG
180 and 255 A
6 AWG
250 MCM
1
350 through 1,200 A
n/a
n/a
1 - 1 MCM = 1000 CM (circular mils)
*
*
Terminal
Terminal
Summary of Contents for 3PCI Series
Page 6: ...Table of Contents 3PCI SCR Power Controller Series Manual iv s Version 1 2 19000325 ...
Page 12: ...Introduction 3PCI SCR Power Controller Series Manual 1 6 s Version 1 2 19000325 ...
Page 22: ...Options Setup 3PCI SCR Power Controller Series Manual 4 2 s Version 1 2 19000325 ...
Page 28: ...Troubleshooting 3PCI SCR Power Controller Series Manual 5 6 s Version 1 2 19000325 ...
Page 32: ...Service 3PCI SCR Power Controller Series Manual 6 4 s Version 1 2 19000325 ...
Page 40: ...Addendum 3PCI SCR Power Controller Series Manual A 6 s Version 1 2 19000325 ...
Page 44: ...Index 3PCI SCR Power Controller Series Manual iv s Version 1 2 19000325 ...
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......