Analog value representation
4.3 Measuring ranges
2AI TC HF analog electronic module (6ES7134-4NB01-0AB0)
Manual, 04/2007, A5E01076892-01
19
4.3
Measuring ranges
4.3.1
Measuring ranges for thermocouples
Introduction
The following tables contain the digitized analog values for the measuring ranges of the
analog input modules.
Since the binary representation of the analog values is always the same, these tables only
compare the measuring ranges with the units.
Measuring range for thermocouple: Type B
Table 4-3
SIMATIC S7 format: Type B measuring range in °C and °F
Units
Units
Type B in °C
Decimal Hexadecima
l
Type B in °F
Decimal
Hexadeci
mal
Range
> 2070,0
32767
7FFF
H
> 3276,6
32767
7FFF
H
Overflow
2070,0
:
1820,1
20700
:
18201
50DC
H
:
4719
H
3276,6
:
2786,6
32766
:
27866
7FFE
H
:
6CDA
H
Overshoot range
1820,0
:
0,0
18200
:
0
4718
H
:
0000
H
2786,5
:
32
27865
:
320
6CD9
H
:
0140
H
Nominal range
-0,1
:
-120,0
-1
:
-1200
FFFF
H
:
FB50
H
31,9
:
-184,0
319
:
-1840
013F
H
:
F8D0
H
Underrange
< -120,0
-32768
8000
H
< -184,0
-32768
8000
H
Underflow