Instruction Guide

Circuit Breaker Handle Replacement Diagram *

Notes:   Toggle on circuit breaker must

* Diagram applies to size 3.5 or 4 starters with E or F frame breaker

Circuit Breaker Assembly Instructions

1.       Remove the two screws that connect the handle link to the 

           pivot assembly.

2.       Use a 5/16 ” wrench to remove the two  1/4-20 screws and 

          lock washers which secure the handle to the enclosure 

          flange. These screws are located on the underside of the 

          enclosure flange. Remove the old handle assembly from 

          the enclosure.

3.       Remove the lever assembly from the panel and replace it 

          with one provided. The mounting panel may need to be 

          removed to access the mounting screws.

4.     Hardware  has  been  provided  to  mount  a  new  circuit 

       breaker  if  necessary.

5.     Install  the  new  handle  assembly  onto  the  enclosure.

6.     Reinstall  the  two 1/4 -20  screws  and  lock  washers.

       Make  sure  the  handle  housing  is  sealed  against  the 

       enclosure flange  as  this  prevents  the  entry  of  moisture.

7.     Reinstall  the  two  screws  that  connect  the  handle  link  to  the 

       pivot  assembly.

9.    Verify  that  the  handle  mechanism  turns ‘ON’ and ‘OFF’  the

       circuit  breaker.

10.    Manually  trip  the  circuit  breaker and  verify  that  the  handle 

       will  reset  the  breaker.

11.   Verify  that  the  door cannot  be  opened  with  the  handle  in 

       the ‘ON’  position.

E87010-A0137-T003-A4

8.     No  handle  adjustment  is  required.

Siemens Industry, Inc. 3617 Parkway Ln, Peachtree Corners, GA 30092   www.usa.siemens.com

         6         A5E31166526A-003    

Replacement Parts and Instruction Guide

Summary of Contents for 17

Page 1: ...sult if proper precautions are not taken Warning Indicates death severe personal injury or property damage can result if proper precautions are not taken Caution Indicates personal injury or property damage may result if proper precautions are not taken Short Circuit Explosion Hazard Can cause death serious personal injury or property damage Fully engage all door latches and spread ends of door hi...

Page 2: ...itch Type Selection Disconnect Fuse Clip Ampere Rating 3 ED63A003 10 ED63A010 25 ED63A025 30 ED63A030 50 ED63A050 100 ED63A100 125 ED63A125 150 FXD63A150L B1 Disconnect Switch Handle and Mechanism Class 17 25 32 Enclosure Type 1 3R 4 4X 12 Disconnect Size Amps Enclosure Size Handle Assembly Only Handle Assembly Disc Mech 3 125 100 125 150 250 24 H x 11 W x 8 D 24 H x 20 W x 8 D 36 H x 24 W x 8 D A...

Page 3: ...th primary fusing KT_ _ 150 is 150VA with primary fusing E Motor Starter or Contactor See device label for appropriate replacement parts sheet F Auxiliary Contacts Not Shown Auxiliary Contacts Installed on contactor 1NO G10 1 49AB10 2NO G20 1 49AB20 3NO G30 1 49AB20 1 49AB10 4NO G40 1 49AB40 1NC G01 1 49AB01 2NC G02 2 49AB01 1NO 1NC G11 1 49AB11 1NO 2NC G12 1 49AB12 2NO 1NC G21 1 49AB21 2NO 2NC G2...

Page 4: ...link to the mechanism The retaining ring should not spin freely on the shaft after it is installed 8 No handle adjustment is required 9 Verify that the handle mechanism turns ON and OFF the circuit breaker 10 Verify that the door cannot be opened with the handle in the ON position 1 Remove the 2 screws from the connecting link 2 Use a 5 16 wrench to remove the two 1 4 20 screws and lock washers wh...

Page 5: ...en provided to mount a new circuit breaker if necessary 5 Install the new handle assembly onto the enclosure 6 Reinstall the two 1 4 20 screws and lock washers Make sure the handle housing is sealed against the enclosure flange as this prevents the entry of moisture 7 Reinstall the two screws that connect the handle link to the pivot assembly 8 No handle adjustment is required 9 Verify that the ha...

Page 6: ...ed to access the mounting screws 4 Hardware has been provided to mount a new circuit breaker if necessary 5 Install the new handle assembly onto the enclosure 6 Reinstall the two1 4 20 screws and lock washers Make sure the handle housing is sealed against the enclosure flange as this prevents the entry of moisture 7 Reinstall the two screws that connect the handle link to the pivot assembly 9 Veri...

Reviews: