IV431E REV. 00 Issued: 2020/11/16 User Manual Soleil SPX 200K-250K
Pag. 68 of 76 +FR
Items
Min.
Typical Max.
Illustration
Frequency range (Hz)
48
50
50.5
Settable (If it is necessary to set
the parameter, please contact the
manufacturer.)
Max. inverter backfeed current to
the array (A)
0
Max.
output
over-current
protection (A)
250
Max. output fault current (A)
758
Current (inrush) (A)
8.93
Grid-tied inverting efficiency
-
-
99.0%
-
Grid-tied China efficiency
-
-
98.5%
-
Grid-tied current harmonic
-
-
3%
Full-power
Power factor range
0.8
Leading
1
0.8
Lagging
-
Current DC component (mA)
<812
-
Output current (A)
-
-
178.6
-
Protection grade (IP)
IP66
-
Isolation type
No isolation
With no transformer, the input
cannot be connected with ground,
or the grounding output must be
with isolation transformer.
Heat dissipation
Smart wind-cooling
-
Noise
<75
f
2dBA@1m
Do not install in a noise-sensitive
environment
Human Interface
LED indicator
-