Optional Accessories -
LSB-Moduel with 4 Digital Outputs
92
9.3.5 Technical
Specifications
Output Module
• Rated voltage UN
• Current
consumption
• Power
consumption
• Operating voltage range
• Response time (from
receiving to relay switching)
• Release time (from receiving
to relay switching)
• Recovery
time
• Operating
temperature
range
• Storage temperature range
• Suppressor
circuit
• Relay status display
• Function
display
• Operation
display
• Special
features
• Item
number
• Item number of external
power pack
• 24 V DC
• 100
mA
• 2.4
W
• 0.8 - 1.1 x U
N
• 15 ms (msec)
• 15 ms (msec)
• 200
ms
(msec)
• 0 °C to +55 °C (-4 °F to 130 °F)
• -25 °C to +70 °C (-13 °F to 158 °F)
• Polarity reversal protection for operating voltage
• LED
• Green LED for BUS activity and supply voltage
• Red LED for BUS error messages
• Manual operation level with confirmation via BUS
• 663R4027S (with connection cable)
• 663R4024
Digital Outputs
• Output
contact/material
• Switching voltage
• Max. making/breaking current
• Continuous current
• Protection of contacts
• Mechanical
durability
• Contact
life
• Permissible number of
operations (cycles) per hour
• Insulation in accordance with
VDE 0110
• Rated voltage
• Overvoltage
category
• Contamination level
• Coil/contact test voltage
• Contact/contact test voltage
4 NO contacts / AgNI
• max. 250 V
• 12 A / 4 s at 10 % on period
• 6 A/relay, but max. 12 A/module
• 6
A
1x107 operating cycles
1x105 operating cycles
• 360 at nominal load
C
250 V
II
2
• 4,000 V AC 50 Hz 1 min
• 1,000 V AC 50 Hz 1 min
Housing
• Degree of protection (EN60529)
• Connection cross-section of
device terminals
• Connection cross-section of
screwable plug-in terminals
(BUS, power supply)
• Weight
• Housing dimensions (W x Hx D)
• Housing: IP50, terminals: IP20
• 2.5 mm² (0.038 in
2
)
• 1.5 mm² (0.023 in
2
)
• 95 g (0.2 lb)
• 35 x 68 x 60 mm (1.4 x 2.7 x 2.4 in)