background image

Minimum

Typical

Maximum

Control voltage S33/S11 and S21
Control voltage

17.4 V DC 

22 V DC

26.4 V DC

Control current

40 mA

100 mA

Short-circuit current between S33/S11 and S21

300 mA

Fuse

Electronic fuse

Response time in case of cross-circuit

50 ms

Switch on time after cross-circuit

50 ms

Electrical isolation between A1/A2 and S21, S11, S33   No

Input circuits (S12, S31, S22, S34, S35)
Input voltage (S12 and S31)

HIGH

17.4 V DC

26.4 V DC

LOW

–3V DC

+5 V DC

Input current S12 and S31

40 mA

100 mA

Input current S34/S35

5 mA

50 mA

Reset time

Manual reset (S34)

40 ms

Automatic reset

(ESPE: S33/S35; tactile: S12/S35)

80 ms

Reset button operation time

50 ms

Minimum shutdown time/minimum switch-on time

7 ms

Permissible test pulse duration/test frequency

1000 µs/

10 s-1

Cable resistance on the input circuit

35 Ohm

Output current circuits (13/14, 23/24, 33/34)
Reactivation delay (K1/K2)

25 ms

Minimum switch off time

70 ms

130 ms

Contact material and surface finish

Ag Sn O

2

 + 2µ Au

Enable current paths (normally open contact), safety

relevant

3

Contact type

Positively guided

Max. contact load (see diagram)

Switching voltage AC

10 V

230 V

Switching voltage DC

10 V

300 V

Switching current

10 mA

6 A

Total current I

sum

12 A

For UL 508 and CSA applications

Switching voltage AC

230 V

Switching current

6 A

Total current I

sum

12 A

AC-15 Ue 230 V AC, Ie 4 A (360 switching

operations/h)
AC-15 Ue 230 V AC, Ie 3 A (3600

switching operations/h)

Usage category (EN 60

 

947-5-1)

DC-13 Ue 24 V DC, Ie 4 A (360 switching

operations/h)
DC-13 Ue 24 V DC, Ie 2.5 A (3600

switching operations/h)

Contact fuse protection gG

6 A

Permissible switching frequency

3600/h

Service life, mechanical

10

7

 switching operations

Minimum

Typical

Maximum

DC contact current-breaking capacity

Service life, electrical

Operating data
Protection against physical contact (EN 60

 

664-1,

EN 60

 

947-1)

Rated impulse voltage V

Imp

 (

EN 60

 

664-1)

4 kV

Overvoltage category

II

Rated voltage

300 V AC

Radiated emissions

EN 61

 

000-6-4

Interference resistance

EN 61

 

000-6-2

Test voltage U

rms

 50 Hz

2 kV

Enclosure rating

Housing

IP40 (EN 60

 

529)

Terminals

IP20 (EN 60

 

529)

Mounting

Mounting rail (EN 60

 

715)

Ambient operating temperature

–25 °C

+55 °C

Storage temperature

–25 °C

+75 °C

Wire cross-sections

Single wire (1×)

0.14 mm²

2.5 mm²

Single wire (2×, same cross-section)

0.14 mm²

0.75 mm²

Fine stranded wire with ferrules (1×)

0.25 mm²

2.5 mm²

Fine stranded wire with ferrules (2×, same cross-

section)

0.2 mm²

0.5 mm²

Allowed tightening torque

0.5 Nm

0.6 Nm

For UL 508 and CSA applications

Connection cross-section

AWG 26-14

(only use 60/75 °C copper flexible wire)

Tightening torque

5-7 lb⋅in

Weight

210 g

13.2 Dimensional drawings

Fig. 7:  Dimensional drawing UE48-3OS with screw type terminals (mm)

Fig. 8:  Dimensional drawing UE48-3OS with removable terminals (mm)

Switching voltage (V DC)

Switching operations

S

w

itc

hi

ng

cu

rr

en

t

(A

)

S

w

itc

hi

ng

cu

rr

en

t

(A

)

L/R = 40 ms

t

LB

 > 5 ms

L/R = 0 ms

t

LB

 < 5 ms

L/R = 40 ms

t

LB

 < 5 ms

Contact

clearance:

1.2 mm

t

LB

: Arc duration

AC-15: 230 V

DC-13: 24 V

DC-1: 24 V

AC-1: 230 V

Reviews: