6.4
Overview of connections
1
2
3
4
Figure 2: SIM200 connection overview
1
POWER: Input of voltage supply
2
CONFIG: Configuration with SOPAS ET
3
S1-S4: 4 x sensor connections for IO-Link sensors and sensors with digital inputs and
outputs
4
P1-P2: 2 x Ethernet connections
6.5
Pin allocation of the connections
6.5.1
POWER
3
4
2
1
Table 2: POWER pin assignment, M12 - 4-pin, A-coded, male
PIN
Signal
Function
1
+24 V IN
IN1 supply voltage, max. 4 A
2
NC
Not connected
3
GND
Ground
4
NC
Not connected
ELECTRICAL INSTALLATION
6
8026126//2020-10-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | SIM200
17
Subject to change without notice