Operating instructions Register sensors RS25
Description of the operating modes and parameters
36
© SICK AG • Presence Detection • Subject to change without notice • 8015887
9.3
Oscilloscope mode
The following table describes the "Oscilloscope mode":
Description
Function
In this mode, the sensor sends the raw data of the light re-
mission values for all three colors of red, green, and blue,
or for just one color, in a cycle.
→
See the figure below.
Activation
This mode must be activated via Ethernet Powerlink in
the "Operation mode" field. This mode must be deactivat-
ed again via the "Operation mode" field. The parameter
"T
0
-Trigger“ is not used for this mode.
Prerequisite
The following parameters must be set before starting:
• Timing resolution: 4 µs to 250 µs
• Sending color: "red", "green", "blue",
or "red + green + blue"
Feedback
The following data is sent from the sensor to the PLC.
• Mode changes or faults
• Raw data of the light remission values for the selected
colors. Timing values are relative to the Ethernet Power-
link NetTime.
Speed
The maximum speed is not restricted for this mode.
Table 9:
Oscilloscope mode
Start
Stop
Fig. 21: Explanation of Oscilloscope mode