9. TECHNICAL DATA
9. Technical data
Technical data
Measuring range
Measuring range
See type label
Overload protection
Overload protection refers to the sensor element used. Depending on the process connection and
seal used, the overload protection could be limited.
≤ 600 bar (< 8,702 psi): 2-fold
1,000 bar (14,504 psi): 1.5-fold
Increased overload protec-
tion (option)
Deviating temperature errors, signal noise and long-term stability occur with increased overload
protection.
Vacuum-tight
Yes
Digital display
Type
14-Segment LED, red, 4-digit, character height 9 mm (0.35 in)
Display can be rotated electrically by 180°
Output signal
Output signal
See type label
Load resistance
4 ... 20 mA
≤ 500 Ω
DC 0 ... 10 V
> Max. output voltage / 1 mA
IO-Link (option)
Version 1.1
Zero point adjustment
Max. 3% of the range
Analog output/Switching
output attenuation
Can be configured from 0 ms ... 65 s
Power-up delay
1 s
Switching thresholds
Switching point 1 and switching point 2 can each be adjusted individually
Switching functions
Normally open, normally closed, window, hysteresis (freely adjustable)
Switching voltage
Auxiliary energy – 1 V
Switching current
Max. 250 mA