Delay times (0 ... 50 s)
This makes it possible to filter out unwanted pressure peaks of a short
duration or a high frequency (damping).
The pressure must be present for at least a certain pre-set time for the
output to switch on. The output does not immediately change its status
when it reaches the switching event (SP), but rather only after the pre-set
delay time (DS).
If the switching event is no longer present after the delay time, the switch
output does not change.
The output only switches back when the system pressure has fallen down
to the reset point (PR) and stays at or below the reset point (RP) for at
least the pre-set delay time (DR).
Fig.: Delay times