6 Set up with the display and adjustment module
LBR • Two-wire 4 … 20 mA/HART
62273-EN-200520
In the menu item "
Current output Min./Max.
", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
In the menu item "
Lock/unlock adjustment
" you safeguard the sensor
parameters against unauthorized or unintentional modifications.
With active PIN, only the following adjustment functions are possible
without entering a PIN:
•
Select menu items and show data
•
Read data from the sensor into the display and adjustment module
Releasing the sensor adjustment is also possible in any menu item by
entering the PIN.
Caution:
With active PIN, adjustment via PACTware/DTM and other systems is
also blocked.
This menu item enables the setting of the requested national lan-
guage.
The following languages are available:
•
German
•
English
•
French
•
Spanish
•
Russian
•
Italian
•
Dutch
•
Portuguese
•
Japanese
•
Chinese
•
Polish
•
Czech
•
Turkish
In the delivery status, the LBR is set to the ordered national language.
In this menu item you can define the way measured values are indi
-
cated on the display.
Setup - Current output
Min./Max.
Lock/unlock setup - Ad-
justment
Display - Menu language
Display - Displayed value
1 and 2