Operating Instructions
Chapter
5
IOLSHPB-P3104R01
2010-07-16
© SICK AG • Industrial Sensors • Germany • Subject to change without notice
53
Commissioning and operation
Parameters
The “PD-PCP x words” modules do not contain any parameters that can be modified.
The parameters of other modules can be modified accordingly.
Global device parameters:
Operating mode Port n
Digital input (default)
Port n is a digital input.
Port n is a digital output.
Digital output
a
WARNING
An IOLD must not be connected!
SCAN mode
Port n cyclically attempts to establish IO-Link
communication. If an IOLD is detected, the
port switches to COM mode. Between com-
munication attempts the port behaves like a
digital input.
SIO input with IO-Link
access
Port n is a digital input. During read or write
access by the application to an IOLD
connected to this port, an attempt is made
to establish IO-Link communication. If an
IOLD is detected, access is executed in
accordance with the parameterized IOLD-ID.
If no IOLD is detected, the communication
attempts are aborted after around 5
seconds.
ID-specific diagnostics
Enable (default)
ID-specific diagnostics are active.
Disable
ID-specific diagnostics are not active.
Module status diagnostics
Enable (default)
Module status diagnostics are active.
Disable
Module status diagnostics are not active.
Channel-specific diagnostics
Enable (default)
Channel-specific diagnostics are active.
Disable
Channel-specific diagnostics are not active.
IOL status diagnostics
Enable (default)
IOL status diagnostics are active.
Disable
IOL status diagnostics are not active.
IOLM diagnostics
Enable (default)
The events of the IOLD at port n are acknow-
ledged and mapped to the PROFIBUS
diagnostics.
Disable
The events of the IOLD at port n are only
acknowledged.