6 Overview of default settings
42
8013863/10L9 /2018-08-01 © SICK AG • Fluid sensors • Germany • Subject to change without notice
The following settings are necessary:
Adjustment of puls output in the menu
Digital Output Q1/Q2 ==> Function ==> Pulse Output
Options Output ==> Pulse Value ==> e.g. 1 ml per pulse
6 Overview of default settings
Function
Default settings
Digital output 1 (Q1)
Pulse output
Digital output 2 (Q2)
Empty pipe output
Digital input 1 (IN1)
No function assigned
Current output (QA)
4 mA … 20 mA
Pulse value
1 ml/pulse
Creeping suppression
0.3 l/min at NW10
0.9 l/min at NW15
3.5 l/min at NW20
5.0 l/min at NW25
6.1 General instructions
The following checks should be carried out before the measuring device is switched on for the first
time:
■
Check the electrical connections and the cable configuration
■
Check the measuring device mounting position. Is the direction of the arrow on the housing/type
plate the same as the actual flow direction in the pipeline?
■
Is the sample line completely filled with liquid?
■
Is there a corresponding counterpressure?
The FFU is ready for operation.