Figure 17: Prevention of equipotential bonding currents in the system configuration by the use of
electro-optical signal isolators
1
IO controller (PLC)
2
Metal housing
3
Electro-optical signal isolators
4
Optical fiber
5
Shielded electrical cable
6
Power supply
7
Grounding point 2
8
Grounding point 1
The use of electro-optical signal isolators between the islands isolates the ground loop.
Within the islands, a stable equipotential bonding prevents equalizing currents on the
cable shields.
Measures for small system installations
For smaller installations with only slight potential differences, insulated mounting of the
device and of peripheral devices may be a sufficient solution.