7. Fehlersuche für Basisgerät CDM420

Wichtig!

 

Fehlersuche in Zusammenhang mit optionalen Modulen siehe 
jeweils deren Betriebs- oder Montageanleitung.

7. Troubleshooting for CDM420 (Basic Device)

Important!

 

For troubleshooting of the optional modules see the respective 

operating instructions or fitting instructions.

Aufbau, Klemmenbelegung/

design, terminal assignment

Schema: Aufbau eines SICK CAN-Sensor-Netzwerkes

 

Diagram: Building a SICK CAN sensor network

Konfigurationsschalter

 

Configuration switches

Anschluss für ID-Sensor

ID sensor connectio

n

Klemmleisten für  

Verdrahtung 

Terminal strips for wiring 

Anschluss PC

PC connection

Konfigurationsschalter

 

Configuration switches

Klemmleisten für  

Versorgungsspannung 

Terminal strips for power 

supply voltage

LEDs

CAN bus

“Host“

“Result 1“
“Sensor 1“

ID sensor

CDM420-0006

ID sensor

ID sensor

CDM420-0006

CDM420-0006

+24 V* = Versorgungsp24 V nach Schalter S1 und interner Sicherung.

+24 V* = Power supply v24 V behind switch S1 and internal fuse.

 

Störung

  Nach Anlegen der Versorgungs-

spannung U

IN

 leuchtet die LED  

„Power“ (U

IN

*) nicht

  Nach Anschluss des PCs an  

den Stecker „AUX“ kein Zugriff 
auf den ID-Sensor mit Konfigu

-

rationssoftware SOPAS-ET 
 
 
 
 
 
 
 
 
 

  Signale des angeschlossenen 

Lesetakt-Sensors bleiben 

 

wirkungslos im ID-Sensor

 

 
 
 
 
 

Abhilfe

  Schalter S 1 (Power) in Position 

„ON“ bringen

 

  Wenn kein CMC600 gesteckt, Schal

-

ter S 8 in Position „NO“ bringen

  SOPAS-ET: Erforderliche Gerätebe-

schreibungsdatei für betreffenden 
ID-Sensor nicht vorhanden oder für 
anderen Firmwarestand als vorlie-
gendes Gerät.  
Passende Gerätebeschreibungs-

datei in SOPAS-ET über Funktion 
„Gerätemanager“ nachladen und 

einbinden.

  SOPAS-ET: Mit Funktion „Gerätesu

-

che“ die Kommunikation mit dem 

ID-Sensor aufnehmen

  Lesetakt-Sensor gemäß Betriebsan

-

leitung des ID-Sensors anschließen

  Stellung des Schalters S 6 prüfen 

(SGND–GND)

  Mit SOPAS-ET die Quelle des Lese-

takts im ID-Sensor auf „Sensor 1“ 

einstellen.  
Download zum ID-Sensor durchfüh-
ren!

Remedy

  Set switch S 1 (Power) to “ON” 

 

  If no CMC600 is connected, set 

switch S 8 to “NO”

  SOPAS-ET: required device 

descrciption file for the related ID 
sensor not existent or file related 
to an other firmware version as the 

current device uses.  
Reload and insert the suitable 

device descrciption file in SOPAS-

 

ET using the “Device manager” 
function.

  SOPAS-ET: Using the “Device 

search” function to start the com-
munication with the ID sensor

  Connect reading pulse sensor in 

accordance with the operating 
instructions of the ID sensor

  Check switch S 6 (SGND–GND)

  Using SOPAS-ET software, set the 

reading pulse source on the ID 
sensor to “Sensor 1”.  
Perform a download to the ID 
sensor.

Malfunction

  “Power” LED (U

IN

*) does not  

light up when power supply U

IN

 

is connected 

  Cannot access ID sensor with  

SOPAS-ET configuration soft

-

ware after connecting the PC to 

the “AUX” male connector

 

 
 
 
 
 
 
 
 
 

  Signals from connected reading 

pulse sensor have no effect to 
the ID sensor 
 
 
 
 
 

  Oder ID-Sensor über Ethernet kontaktieren (abhängig vom 

Sensortyp). 

5. Stromversorgung für CDM420 einschalten. 

  Or establish communication to the ID sensor via Ethernet (de-

pends on sensor type)

5. Switch on the power supply for CDM420.

Summary of Contents for CDM420-0006

Page 1: ...t u n g O p e r a t i n g I n s t r u c t i o n s 1 Intended use Modular designed connection module referred to as CDM420 below for connecting one SICK identification sensor referred to as ID sensor below to the host CAN Sensor Network field bus system as well as to the peripheral equipment and power supply Connect the ID sensor using a SICK standard cable to the externally 15 pin D Sub female con...

Page 2: ...ew in 6 2 Supply voltage Page 3 and 8 Technical Data Page 6 CLV69x bar code scanner optional cloning plug A no 2062450 or cloning plug B no 2062452 Input voltage of 100 V to 250 V AC 50 Hz to 60 Hz is required when using the CMP490 Power Supply Module 4 Installation Free access to internal AUX RS 232 male connector is re quired to connect to the ID sensor configuration and diagnosis Max cable leng...

Page 3: ...CMC Integration des CMC600 NO oben YES CMC in Leitung der Aux Schnitt stelle des ID Sensors geschaltet NO Kein CMC gesteckt Switch Function Default S 2 RS 485 RS 422 485 selector OFF ON RS 485 OFF RS 422 S 3 Trm422 RS 422 termination receiver OFF ON 120 Ohm resistor connected OFF No termination S 4 TrmCAN CAN bus termination OFF ON 120 Ohm resistor connected OFF No termination S 6 SGND GND Referen...

Page 4: ...am on Page 5 or inside the cover Use shielded cables to establish an EMC compatible connection between host interface and host To prevent interference do not install cables parallel to power supply or motor cables e g cable ducts Choose reference potential for switching inputs with switch S 6 Electrical Installation Procedure 1 Connect the ID sensor cable to the 15 pin D Sub HD female connector on...

Page 5: ...AS ET Erforderliche Gerätebe schreibungsdatei für betreffenden ID Sensor nicht vorhanden oder für anderen Firmwarestand als vorlie gendes Gerät Passende Gerätebeschreibungs datei in SOPAS ET über Funktion Gerätemanager nachladen und einbinden SOPAS ET Mit Funktion Gerätesu che die Kommunikation mit dem ID Sensor aufnehmen Lesetakt Sensor gemäß Betriebsan leitung des ID Sensors anschließen Stellung...

Page 6: ...DM420 0006 Blindplatte ohne Anschlüsse oder Platte mit IP 65 An schluss 5 In Ruhe keine Montage oder elektrische Installation sonst bis 20 C 8 Technical Data Type CDM420 0006 No 1058634 Visual indicators 5 x LEDs Electrical connections 1 x female connector D Sub HD 15 pin 1 x male connector D Sub 9 pin Screw terminals for wires 0 14 mm2 2 5 mm2 approx 26 AWG 13 AWG Spring terminals for wires 0 14 ...

Page 7: ...H6xx Lector6xx Only Maßbild dimensioned drawing Alle Abmessungen in mm inch All dimensions in mm inch Anschlussraum für Stecker Space required for connector Anschlussraum für Stecker bei optionaler Blende mit Steckverbindungen Space required for connectors when using optional face plate with plug in connections CLV6xx RFU6xx RFH6xx Lector6xx Only ...

Page 8: ...one 39 02 27 43 41 E Mail info sick it Japan Phone 81 0 3 5309 2112 E Mail support sick jp Malaysia Phone 603 808070425 E Mail enquiry my sick com Netherlands Phone 31 0 30 229 25 44 E Mail info sick nl New Zealand Phone 64 9 415 0459 0800 222 278 tollfree E Mail sales sick co nz Norway Phone 47 67 81 50 00 E Mail sick sick no Poland Phone 48 22 837 40 50 E Mail info sick pl Romania Phone 40 356 1...

Reviews: