User’s Manual     15

 

 

 

Page 

B.01

 reports status information related to the 

PMCB

 network. This includes the number of 

network devices, the operating mode of the load function, the identifier of the pilot generator and 
the list of priorities. 

Page 

B.02

 shows the measurements concerning the generation of energy by the single generators 

and all the generators in the 

PMCB

 network. 

Page 

B.03

 shows the value of the active and reactive powers for each generator connected to the 

BUS

 line. 

Pressing 

ENTER

 

 in this mode, opens the programming menu of the load function 

parameters directly. 

See the following document for the meaning of the parameters: 

EAAM0193XX(Parameters 

Table). 

 

 

 

In this mode, you can access events and data recording databases. 

A number and time/date stamp identify each record. 

The  number  is  shown  in  the  top  right  line  of  the  multifunctional  display  with  the  total  number  of 
records. 
When  the  archive  is  full,  a  new  record  overwrites  the  old  one;  so  the  identification  number  may 
change in time. 

Enable the mode with the 

ENTER

 

 button. A menu will guide you through the selection of the 

required function. 

 

 

 

 

 

 WARNING: Before proceeding with manual synchronization, check the 

configuration is set so the circuit breaker cannot close in the case of a phase speed 
alignment error. 

 

With the lockable selector in the 

MAN

 position, depending on the plant type and on how the panel 

is wired, you can command the closing of the 

GCB

 or 

MCB

 with manual synchronization. 

In order to use this procedure, the 

DICHRON

 expansion module or an external (

SINCHRO-

CHECK

) synchroscope must be installed. 

In 

MAN

 mode, with the engine and the generator running and network/bus voltages present (

BUS 

LIVE

 indicator steady on), the function can be activated by pressing the button of the open circuit 

breaker (

MCB

 

 or 

GCB

 

 ). 

When the button is pressed, the circuit breaker will not close, but the manual 

SYNCHRO

 function is 

activated and synchronization page 

M.04

 is displayed automatically. If the 

DICHRON

 module is 

used, the page will display a synchroscope, otherwise the external synchroscope will be powered. 

Summary of Contents for DST4601/PX

Page 1: ...Filename EAAM019704EN docx Rev 04 Date 08 05 2013 ID Document EAAM0197 Product DST4601 PX...

Page 2: ...codes 11 2 5 1 2 Setting the parameters 12 2 5 1 3 How to input string value 13 2 5 1 4 Direct access to the previous page 13 2 5 1 5 Alarms and protection parameters 13 2 5 2 Status information S xx...

Page 3: ...WER OFF is used to indicate a fault that prevents the generator from operating and causes the standard automatic engine shutoff including a cooling phase WARNING is used to indicate a fault that requi...

Page 4: ...is required AUTO TEST Gen set is in automatic mode all the functions are controlled automatically The combination of the buttons START and MODE lets you activate deactivate the TEST mode the STOP but...

Page 5: ...crease the engine speed if set to synchronized or the power supplied if in power mode ENTER Lets you enter the programming mode and open submenus change a variable and confirm the operation Furthermor...

Page 6: ...rogramming parameters in the version with CANBUS it also lets you force the exit from BUS OFF mode START In MAN mode it is used to start the generator In AUTO mode it is used with the MODE button to e...

Page 7: ...at a command is being sent from one of the serial ports the second serial port is managed in signalling only if configured as the COM port and not the I O expansion Indicates at least one of the two s...

Page 8: ...open after a closing command Flashing at 75 ON if the KG is closed after an opening command Flashing at 50 in synchronization phase with BUS LIVE indicator GCB The MCB is open The MCB is closed Flashi...

Page 9: ...ed to navigate between the modes Use the LEFT and RIGHT buttons to display the pages in the mode In some modes ex mode P xx and mode H xx to display the pages press the ENTER button and then the UP an...

Page 10: ...rrow buttons or both indicates there are other pages which can be viewed using the relevant LEFT and RIGHT buttons E 01 ENGINE 03 04 06 18 23 Press Bar Temp C Level Oil xx x xxx x xx x Coolant xx x xx...

Page 11: ...t only be changed by qualified personnel Parameters can be protected by password see par Access codes This mode lets you display and change the programming parameters Each programming parameter has a...

Page 12: ...displayed press EXIT to return to the previous menu and try opening the page again The set access code remains in the memory for about 10 minutes after programming has been completed After that it mu...

Page 13: ...exited programming This is the case if no programming operations are performed for 60 consecutive seconds or if the lockable selector is switched to MAN or AUTO Protections and alarms can generally be...

Page 14: ...synchroscope with the main electrical BUS and GENERATOR magnitudes the engine speed and the phase error otherwise the external synchroscope is powered Page S 06 displays the state of the digital input...

Page 15: ...s the old one so the identification number may change in time Enable the mode with the ENTER button A menu will guide you through the selection of the required function WARNING Before proceeding with...

Page 16: ...breaker closes the speed reference is set as close as possible to the nominal value so Gen set can regulate the power properly Warning As some slow power ramps may have been set check the command aga...

Page 17: ...set wait for a few seconds then power it up again Note in this phase do not press the STOP and START buttons Gen set implements the full management of the fuel pump to pump fuel from the storage tank...

Page 18: ...ge with the sequence of buttons SHIFT and EXIT Pressing the sequence of buttons SHIFT and EXIT again you can change the fuel pump command from MANUAL ON pump on the pump starts and will only stop when...

Page 19: ...the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use t...

Reviews: