User’s Manual 13
For some parameters you will have to set a value for the string data.
In this case, pressing
ENTER
makes the square brackets [ ] around the variable flash, and a
cursor appears under the first character of the string. Using the
LEFT
and
RIGHT
buttons,
you can select which character to change. Use the
UP
and
DOWN
buttons to change the
character selected. Repeat the procedure for each character that needs changing.
Use
ENTER
(confirm) or
EXIT
(abort) to end the procedure.
You can open the last programming page displayed directly. This is possible if, when exiting
programming mode, instead of going back though the menus until you exit programming, you hold
down
EXIT
for approximately 2 seconds.
The same is true when accessing the programming mode after Gen-set has automatically exited
programming. This is the case, if no programming operations are performed for 60 consecutive
seconds or if the lockable selector is switched to
MAN
or
AUTO
.
Protections and alarms can generally be configured using dedicated variables. Generally, the trip
time can also be configured.
Setting the trip time to 0 disables the protection.
In this way, information on the system status is provided.
You can scroll through the various pages using the
LEFT
and
RIGHT
buttons.
Page
S.01
displays information on the system status. Part of this information is shown on the bottom
status bar.
The alarms page
(S.02)
is displayed automatically in the case of an anomaly. This page also
contains the diagnostic information on motors with the
J1939
or
MTU
interface.
- communication status of
bus.
There are three possible indications:
-
ERROR-ACTIVE
: normal operation
-
ERROR-PASSIVE
: communication is working despite faults (errors).
-
BUS-OFF
: Gen-set has interrupted the connection to the bus due to too many errors.