background image

 

 

                                                                                                                                  

User’s Manual    9

 

With suitable settings in the following registers we can also choose the source of adjustment and limit 
the range of the output current loop: 

 

40019 

40019 

Select an adjustment 
source 

0 = from trimmer, 1 = from 
Modbus,  2  =  Modbus  + 
trimmer for fine tuning (+/- 
12.5%) 

-

 

By setting the register to 0 the MIN, MAX values are only acquired by the trimmers. 

-

 

By setting the register values to 1 the MIN, MAX values are only read by the following registers: 

 

40004 

40004 

MAX - Max. PWM value (0-
8191) value that can be set 

Writing max. PWM value 

40005 

40005 

MIN - Min. PWM value (0-
8191) value that can be set                               

Writing min. PWM value 

-

 

By setting the register to 2, the MIN, MAX values are read by the above registers and the trimmers 
can be used for fine /- 12.5% in relation to the value set in the register. 

The buttons (except the UP button) and the RAMP and RESET trimmers are no longer read. Only the 
MIN and MAX trimmers and the analog input selected with the UP button are read, this is to minimize 
the response time between input and output variations as far as possible. 

To change mode, move SWC switch SW1, then turn the device off and on again. 

If the SWC switch isn't installed on the board, DIPOT can only function in the normal operating mode. 

 

 

Depending  on  the  DIPOT  version,  you  may  have  an  RS485  communication  interface  or  CANBUS 
interface isolated from the I/O and internal logic circuits; this results in high immunity to transient voltages 
and eliminates problems caused by differences in the input voltages of the devices connected by bus. 
This is particularly useful for long connections, in environments prone to disturbance, or where there is 
no guarantee of equipotential grounding between devices (e.g. direct connection to a PC). 

When initially setting up the device you can use the serial port on 3.5 mm stereo jack connector 

J6.

 This 

serial port is non-isolated (unlike those on connector 

J4

) and can be configured as RS485 or RS232 

using 

SWD

 dip 3. If it is setup as interface RS485 a termination  resistor can be used (as required by 

standard TIA/EIA-485) to close 

SWD

 dip 1. 

The line termination must not be switched in if interface RS232 is selected, or the serial port will 
malfunction. 

The baud rate of the port can also be set (

SWD

 dip 4). 

In the versions with isolated RS485 (

E6102094300xx

 and 

E6102094301xx)

 serial port of connector 

J4

 

is shared with connector 

J6

. Use 

SWD

 dip 2 to select which port should be used. The serial ports on 

J4

 

and 

J6

 cannot operate simultaneously. 

If the serial port is used on connector 

J6

, disconnect the female connector on 

J4.

 

Use 

SWD

 dip 2 as follows, to select which port will be used: 

 

 

If 

SWD

  -2  is  ON,  the  serial  will  be  available  on  connector 

J4

  (RS485  isolated  with  baud  rate 

selected by 

SWD

-4). 

Summary of Contents for DIPOT

Page 1: ...Filename EAAM024505EN docx Rev 05 Date 07 05 2013 ID Document EAAM0245 Product DIPOT...

Page 2: ...tion 4 2 4 Digital inputs 6 2 5 Analog Inputs 6 2 6 Adjustments 7 3 Voltage isolator mode 8 4 Connections 9 4 1 RS485 interface version connections 10 4 1 1 Modbus addresses and communication protocol...

Page 3: ...and piloted with UP and DOWN digital inputs or by modifying the Modbus protocol registry value via RS485 connection or CANBUS J1939 connection to our generator management boards DST4601 DST4601PX DST...

Page 4: ...ng The maximum current absorption is approximately 80 mA at a voltage of 10V The input voltage range is between 7 5 and 32 VDC Configuration J5 PIN 1 positive input J5 PIN2 negative input J3 PIN6 Grou...

Page 5: ...BUS or digital input J3 2 If the input is active the nominal speed is 1800 rpm if the input is inactive the nominal speed is 1500 rpm Switch SWD is a 4 way switch and sets the properties of the availa...

Page 6: ...ates an order of magnitude for the output value LED flashing slowly 50 on and 50 off minimum output value As the output value increases so does the frequency of the flashing 50 on and 50 off Led on wi...

Page 7: ...e at a fixed value The value range can be adjusted observing the relative position of the trimmers the limits minimum and maximum are directly proportional to the angles of rotation of the respective...

Page 8: ...main lit in this mode In this mode SWE dip switches 5 to 8 are no longer read and a CanBus interface will be disabled Using digital input UP PIN 5 of J5 you can select which digital input will be used...

Page 9: ...you may have an RS485 communication interface or CANBUS interface isolated from the I O and internal logic circuits this results in high immunity to transient voltages and eliminates problems caused...

Page 10: ...DO NOT USE pin 1 of J4 GND RESERVED A 120 ohm termination resistance should be connected directly to terminals 4 and 2 of J4 On the DIPOT board there is a dip switch selector that can be used to impl...

Page 11: ...30006 TR2 trimmer TR103 RESET 0 3FF Read value set on trimmer RESET 10bit 30007 30007 Trimmer TR1 TR102 RAMP 0 3FF Read value set on trimmer Ramp 10bit 30008 30008 INPUT 0 5V 0 1023 10 bit Read value...

Page 12: ...egister the result of the test is 0 not performed 1 OK 2 Error 30026 30026 Minimum value of 0 5V input in points per voltage isolator 30027 30027 Maximum value of 0 5V input in points per voltage isol...

Page 13: ...0213 TEST CANBUS received messages counter 30221 30221 RPM value received via CAN BUS RPM x 8 E g 1200 8 1500 RPM 30222 30222 RPM GAP received via CAN BUS If 1500 rpm GAP 120 x 8 960 30223 30223 RPM G...

Page 14: ...CANBUS line with our boards DST4400 DST4601 DST4601PX GC310 GC350 and GC500 The CANbus interface should not be powered from an outside source as it powered by a DC DC source in the device Connect the...

Page 15: ...utput current This switch depends on the type of speed regulator used DIP 7 REMOTE LOCAL CONTROL it should be ON so the current loop output value is determined by the CANBUS command DIP 8 Rpm1500 1800...

Page 16: ...16 User s Manual DIPOT MODULE...

Page 17: ...the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use t...

Reviews: