D-PRO Protection relay Technical Manual
1.3
D-PRO is a protection relay for the genset. It includes all the necessary functions to acquire
the measurements of the plant and to activate one or more outputs in order to keep the plant
safe in case of irregular values acknowledged. The system is not equipped by a multifunctional
display, but it requires the connection to the DST4602 controller for a complete use with the
visualization of the faults and the measurements of frequency, voltage, current and power of
the plant. In case of “stand-alone” use (without connection to the DST4602 controller), the D-
PRO protection relay carries out the same basic functions, but the information are displayed
through LEDs.
1.3.1
The following table shows the protections implemented:
Protection
Description
1
27
Minimum generator's voltage
2
27T
Minimum generator's time-dependent
3
32P
Maximum active power
4
32Q
Maximum reactive power
5
46
Negative sequence
6
47
Wrong phases sequence
7
50
Short circuit
8
50N
Neutral short circuit
9
50V
Short circuit with voltage-restrained
10
51
Maximum current
11
51N
Maximum neutral current
12
51V
Maximum current with voltage-restrained
13
59
Maximum generator's voltage
14
59N - 59V0
Maximum residual voltage (homopolar voltage)
15
81O
Maximum generator's frequency
16
81U
Minimum generator's frequency
17
87G
Genset earthing differential protection
18
32RP
Active power reverse
19
32RQ / 40
Reactive power reverse / Loss of excitation
20
64
Restricted earth fault / Maximum differential current
1.4
For the appropriate use of this manual it is required knowledge of the use and of the
installation of generator groups.
WARNING
!!!
Every operation must be carried out by skilled personnel. There are dangerous voltages on
the terminals of the device; before carrying out any operation on them, ensure you have
opened the mains and genset circuit breakers or removed the related fuses.