Solar working station operation manual SR881
- 37 -
4.5.5.1 tSTP Pump interval- time
Setup steps:
To access main menu FUN, then select submenu tSTP, “tSTP 30” displays on screen.
►Press “SET” button, parameter “30” blinks on screen,
factory set is “30” minutes.
►Press “+”“-” button to adjust the loading time, adjustable
range: 2
~
60 minutes,
►Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
4.5.5.2 tRUN Pump running time
Setup steps:
To access main menu FUN, then select submenu tRUN, “tRUN 15” displays on screen.
►Press “SET” button, parameter “15” blinks on screen, factory set is 15 seconds. .
►Press “+”“-” button to adjust the running time,
adjustable range: 5
~
120 seconds
►Press “ESC” button to exit the menu or wait for 20
seconds to exit automatically, parameters are saved
automatically.
4.6 HND Manual mode
When using this controller first time or when debugging this controller, output of this
controller
(
P1
,
P2,H1
)
can be triggered manually “On, OFF” control.
Setup steps:
To access main menu HND,
-------------------------------------------------------------------------------------------------------------------------
►Press “SET” button, “HND1 off” displays on the screen, P1 output manually set
►Repress “SET” button, “HND1 on” displays on the
screen, P1 output is switched-on
►Repress “SET” again, “HND1 off” displays, P1output is
switched-off
►Press “ESC” to exit P1set program
_________________________________________________________________________
►Press “+” button, “HND2 off” displays on the screen, P2 output manually set
►Press “SET” button, “HND2on” displays on the screen, P2 output is switched-on