Points to be checked during trial operation
Maintenance and inspection
It is recommended that the product be checked for any abnormal vibrations, noises, and proper insulation
every three months.
Bearing lubrication is not required, as sealed type ball bearing is used for the motor bearing. Grease
life is generally one year, although it varies depending on the operating environment.
Contact
Please contact us at the numbers below for any inquiries about the product or other blowers from Showa Denki.
(1) For specifications of the product or any technical inquires:
●Design Group, Engineering Department, Daito Factory, Showa Denki Co., Ltd.
Phone:
072-871-1069
Fax:
072-875-3874
(2) In case of malfunctions of the product or any complaints, please contact
●Your nearest branch or sales office as listed in the Instruction Manual & Directions.
●Quality Assurance Department, Daito Factory, Showa Denki Co., Ltd.
Phone: 072-870-5707
Fax:
072-870-5709
―3―
(1) Power supply source
(1)
Electromagnetic switch
capacity
(2)
Installation
(3)
Power supply connection
(4)
Switch contact failure
When a wire is not turned on electrically due to power
wire interruption or poor switch contact, etc., the
motor will operate in single-phase, resulting in motor
burnout.
(2) Rotational direction
Check whether the rotational
direction matches the rotation arrow
on the nameplate.
If the rotation is in the opposite direction, replace
two power wires.
(3) Operating static
pressure and electric
current
Use a pressure meter and ammeter to
check if the operating static pressure
and electric current are below the
maximum operating static pressure
and current.
When the operating static pressure exceeds the
maximum value, create a bypass hole to release the air.
(4) Operating status
Check whether the Blower generates
abnormal vibrations or noise.
Please contact Showa Denki.