background image

is design to be used WITHOUT termination boards.

Again   the   service   channel   is   selected   with   a

rotary   switch   and   the   connection   to   the   plant   (or
manifold) is similar to the internal transmitter, only there
is no requirement for the Termination Board.

A 230Vac, 50/60 Hertz supply is required.

Note.  This   is  the   only  item  on   the  SDX-15
system   which   does   not   include   a   mains
termination cover.    Note the warning  label

on the outside of the box.

The   2   core   inter-panel   wiring   is   connected   to

signal   terminals  1   &   2.   The   cable   screen   must   be
connected to and earth point or to the circuit earth.

COMPUTER INTERFACES.

Computer Interfaces are available which will give

volt-free contacts which are closed when a condition is
at   normal.   The   relays   are   grouped   in   blocks   of   four,
giving four conditions plus normal, which is closed only
when  all four conditions  on that  service  are  at  normal.
The services are selected, as in the alarm panel, with a
rotary switch. However, the computer interface has only
one switch for up to 5 services. This switch is set to the

rst service required and the other services will follow in

sequence.  e.g.  if the  switch on  a 3 service interface is
set   to   channel   2   then   the   services   detected   will   be
channels 2, 3,4 &5.

The computer interface is a self contained unit,

supplied as a 1, 2, 3, 4 or 5 service unit. A 230Vac, 50/60
Hertz supply is required, which is connected to terminals
under the mains terminal cover. The 2 core inter-panel
wiring is connected to signal terminals 1 & 2. The cable
screen must be connected to the ``S'' terminal. 

The rating of the relay contacts is 0.5amp,  24V

dc resistive.

NOTE.   Each   SDX-15   central   or   repeater   alarm

has an integral common alarm relay 

tted as standard.

This   relay   opens   when   any   alarm   condition   or   fault
occurs on the panel and is similarly rated.

PLANT TO ALARM INTERFACE.

The plant to alarm interface is a low cost means

of complying with the C11 & HTM02-01 requirements for
indication of alarm status in plant or manifold room. It is
mounted   in   a   clear   fronted   polycarbonate   enclosure
protected  to IP65, making  it weatherproof and  suitable
for use in VIE compound etc. with no further protection.
It consists of the following. 

Four   alarm  conditions  plus  normal  Power  On   &

system fault lamps. A one gas transmitter, connected to
the plant & set to the required channel in the same way
as   a  standard   transmitter.  Four  relays,   giving   volt-free
contacts, closed under normal conditions, for connection
to   other   alarm   systems,   BMS   systems   etc.   A   battery
reserve   to   power   the   system   failure   lamp   and   the
transmitter in the event of power failure.

The plant to alarm interface requires a 230Vac,

50/60 Hertz supply and connection to the two core inter-
panel wiring. 

Note. Being a basic indicator, the plant to alarm

interface has  no audible alarm  or test facility.  Refer  to
the  instruction   sheet   supplied   with   the   plant   to  alarm
interface for further details.

Section 5
SYSTEM DESIGN

If   in   doubt,   please   contact   the

manufacturers.   Errors   can easily   be   recti

ed   at

this stage.

The   system   must   consist   of   a   single   central

panel,   which   should   be   mounted   in   a   area   which   is
manned 24 hours a day. Select the number, location and
size (number of services to be displayed) of alarm panel
as required by C11/HTM02-01. 

Select the location and size of transmitters. Use

internal   transmitters   if   an   alarm   panel   is   in   the  same
room   as   the   plant,   or   a   remote   transmitter   if   no
additional local indication is required.

Remember   that   a   plant   to   alarm   interface   is

cheaper   than   a   one   service   repeater   with   internal
transmitter   for   locations   where   local   indication   is
required.

With   more   than   one   service,   a   repeater   with

transmitter   is   more  economical.   The   distance  between
the   plant   and   the   transmitter   should   be   kept   to   a
minimum,   and   in   any   case   should   not   exceed   100
metres. 

See section 4 if conditions of a service are to be

transmitted from more than one location.

Transmitters   are   supplied   with   termination

boards,   which  must   be   mounted   in   or   adjacent   to  the
plant.

Select Computer interfaces as required.

Section 6
SETTING UP

WARNING.   STATIC   SENSITIVE   DEVICES.
OBSERVE HANDLING PRECAUTIONS.

Set the alarm panel at the central location as a

central by placing the jumper between the centre & right
hand pins on the central selector. Ensure that all other
panels have the jumper between centre & left hand pin. 

Set the power failure mode as required using the

jumper  adjacent  to  the  ribbon  cable  connector.     If  the
any alarm panel is to have full battery operation under
power failure conditions, place the jumper between the
centre and lower pins on the power selector. 

Allocate a channel for each service and enter the

name   of   the   service   on   the   log   sheet   in   the   “Gas
Service''   column.   It   may   be   useful   to   allocate   the
services in the order in which they appear on the central
panel,   although   this   is   not   necessary.   Go   to   each
internal  transmitter  and  set   the  rotary  switch   for   each
service  to the  channel allocated  to  that  service on  the
log   sheet.   Set   the   rotary   switch   on   each   remote
transmitter to the channel allocated to the 

rst service

on  this transmitter. Set  the  channel for  each  computer
interface as for remote transmitters.

Set the rotary switch on each plant to alarm 

interface to the appropriate channel. For each alarm 
panel, set the rotary switch for each service displayed on
the panel to the channel allocated to that service.

If a column is not required e.g. if a spare service 

has been installed for future use, set the rotary switch to
``F'' which switches o

 that column.

Set the four audible switches for each  service as

required (switch number 1 is condition 1, the 

rst lamp 

below normal. If a switch is on, the audible for that 
condition will operate, otherwise it will never sound).

Mount the  front  plate & PCB  onto  the  hinge  by

springing the ends of the hinge apart & 

tting into the

clips on the PCB.

Plug  the  ribbon  cable on  the power  supply into

the   control   PCB.   (it   is   keyed   to   prevent   incorrect
connection).

Switch  on  the  power   to  all  panels,  transmitters

etc. and connect the battery cables, observing polarity. 

The system should now be operational.

No panels will operate if the central panel is not

functioning. In this case, all repeater panels will show an
Incoming Signal (number 1) on the system fault display
when the test button is pushed.

This will also happen if the inter-panel wiring is

reversed  at any panel  or  the wiring  is short circuited.  

Disconnect   each   panel   in   turn   until   the   fault

clears. If it does not, check for short circuits. 

5

Summary of Contents for SDX-15

Page 1: ...issue 11 02 06 2021 The SDX 15 Alarm System for Piped Medical Gases...

Page 2: ...IN TELEPHONE 5 GAS CENTRAL LODGE ALARM IN PORTERS 5 GAS REPEATER COMPUTER INTERFACE SDXPIC 4 CORES 5 CORES 5 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES TYPICAL PLANT ALARM SYSTEM TO...

Page 3: ...on is to be in an alarm condition for a prolonged period e g for pipeline maintenance the re trigger can be prevented by silencing the audible with the Lockout button within the panel large at white p...

Page 4: ...e condition to normal if the condition is not to be used or with a 1k8 resistor if the condition is to be transmitted from another transmitter The resistors are used to prevent a system fault due to s...

Page 5: ...number location and size number of services to be displayed of alarm panel as required by C11 HTM02 01 Select the location and size of transmitters Use internal transmitters if an alarm panel is in th...

Page 6: ...ice fault remains requiring re muting When a condition is to be at alarm condition for a long time the audible can be continuously muted as follows Open the panel and while the alarm condition is pres...

Page 7: ...m fault only appears on one section of the system look for a broken wire or loose terminal between the section with the system fault and the rest of the system Contact Line fault This indicates that t...

Page 8: ...MERGENCY PLANT PLANT FAULT FAULT PLANT PLANT VACUUM AIR MEDICAL CYLINDERS CYLINDERS CYLINDERS CYLINDERS FAULT PRESSURE NORMAL FAULT PRESSURE FAULT RESERVE NORMAL FAULT PRESSURE FAULT RESERVE IMMEDIATE...

Page 9: ...IQUID IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL CHANGE CHANGE IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL CHANGE IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL RESERVE FAULT PRESSURE FAULT...

Page 10: ...llowing standards EN60601 1 2 4th Edition 2015 Emissions Standard for Medical Equipment EN55011 Class A 2016 A1 2017 Emissions Standard for ISM Equipment EN60601 1 2 4th Edition 2015 Immunity Standard...

Reviews: