- 40 -
6.3.2 CH2 Function Group
Available only for the SE2 A.
To enter the CH2 Function Group, follow the procedures below.
(1)
In the RUN mode, press the
key until the left characters appear.
(2)
Press the
key.
For the SE2EA, thermocouple input range selection item appears.
For the SE2RA, RTD input range selection item appears.
For the SE2AA, direct current input range selection item appears.
For the SE2VA, DC voltage input range selection item appears.
Setting items are the same as those of Section “6.3.1 Function Group”. (Pages 30
to 39)
Set up the unit referring to the explanation of Section “6.3.1 Function Group”.
6.3.3 Special Function Group
For the SE2 A, setting items are common to CH1 and CH2.
To enter the Special function group, follow the procedures below.
(1)
In the RUN mode, press the
key until the left characters appear.
(2)
Press the
key. “Set value lock” appears.
Display
Name, Function, Setting Range
Factory Default Value
Set value lock
Unlock
IN
OUT
• Locks the set values to prevent setting errors.
• Selection item:
: Unlock
: Lock 1 (None of the set values can be changed.)
: Lock 2 (Only alarm setting groups can be changed.)
Input sampling period
250 ms
IN
OUT
• Selects the input sampling period.
• Selection item:
: 25 ms
: 125 ms
: 250 ms
Auto-light function
Disabled
IN
OUT
• Selects Auto-light function Enabled/Disabled.
• Selection item:
: Disabled
: Enabled