22
load "SAMPLE1A.BAS"
OK
(5) Execute the sample program.
Input as underlined by key, and press the
(Enter) key.
OK
RUN
When executed, the display appears as follows, it is the standby status for command input.
The transmitting data is displayed above the line [-------], and the receiving data is displayed
below the line.
-------------------------------------------------------------------------------------------------------------------
(6) As Example 1 below, execute the setting command of the main setting value.
(When the main setting value for Program pattern 0, Step 0 is set to 600 [Address: 0])
To execute the command, input it from header (STX) "^B" to data with the key, and press
the
(Enter) key.
(Example 1)
^B P
1 0 0 0 0 2 5 8
Data: 600 (0258H)
Data item: (1000H)
Command type [Setting]: (50H)
Sub address: 0 (20H)
[00H + 20H = 20H]: " " space
Address : 0 (20H)
[00H + 20H = 20H]: " " space
Header: STX (02H)
Press the <B> while the <CTRL> is
being pressed.
The checksum is automatically calculated, and it is sent with the delimiter (ETX).
^B P 1 0 0 0 0 2 5 8 E 0 ^C
Delimiter ETX (03H)
Checksum
When the command finishes normally, it responds as follows.
^F E 0 ^C
Delimiter ETX (03H)
Checksum
Address
Header ACK (06H) Acknowledgement