38
7.10 Set value memory function
Up to 6 groups of SV for the connected controllers can be saved.
If the
key is pressed after selecting Set value memory number in Main setting mode,
SVs in the selected memory number are sent to the connected controllers.
(See p.38 for registering Set value memory number.)
[When a lot of controllers are connected, operations at the next setting mode (SV setting)
cannot be performed until all connected controllers SV changes are completed.]
If set values are changed from the controller side
If set values are changed from the controller side, the LMD-100 reads and saves the
sending items the LMD-100 already has:
Sending items of the LMD-100: SV, Alarm 1 value, OUT1 proportional band, OUT2
proportional band, Integral time, Derivative time, ARW,
OUT1 proportional cycle, OUT2 proportional cycle,
Manual reset, Set value lock, AT/Auto-reset
However, even if SV is changed from the controller side, the SV of the Set value memory
number cannot be changed.
To change SV of the Set value memory number, set it in the “SV setting” mode.
How to register the Set value memory number
(e.g.) When 5 units of controller are connected, 30 types of SV can be registered as follows.
Set value memory No.
Channel No.
1
2
3
4
5
6
1
100
200
150
125
140
230
2
110
210
170
135
150
230
3
120
220
190
120
150
220
4
130
230
210
120
160
220
5
140
240
230
100
160
210
When registering SV in Set value memory number 3
(1) Enter the Main setting mode.
Press the
key in the PV/SV display mode or Data logging mode.
Set value memory number selection mode in the Main setting mode appears.
(2) Select the Set value memory number.
Select Set value memory number “3” with the
or
key, and press the
key.
The unit will proceed to the SV setting mode.
(3) Register the SV.
Set SV with the
or
key, then press the
key.
SV will be registered and the channel will be switched.
Set SV for other channels in the same way as the above.
(4) Revert to the PV/SV display mode or Data logging mode.
Press the
key for 10 times or hold down the
key for approx. 3 seconds.
The unit will revert to the PV/SV display mode or Data logging mode.
To set other Set value memory numbers, follow steps (1) to (4) above.