25
6.7 Main setting mode
SV, Alarm 1 value and PID parameters, etc. of the connected controller can be set.
Press the
key in the PV/SV display mode or Data logging mode.
The unit will proceed to the Main setting mode.
To set (or select) each item, use the
or
key.
Pressing the
key registers the value, and switches the channel number.
Pressing the
key registers the value, and switches the setting item.
Display
Name, Function, Setting range
Default value
Set value memory number
1
CH
MEMO
PV
SV
• Selects the Set value memory number.
• Up to 6 groups of SV of the connected controller can be saved.
If the
key is pressed after selecting Set value memory number,
SVs in the selected memory number are sent to the controllers.
(See p.38 for registering Set value memory number.)
[When a lot of controllers are connected, operations at the next
setting mode (SV setting) cannot be performed until all connected
controllers SV changes are completed.]
• If set values are changed from the controller side, the LMD-100
reads and saves the sending items the LMD-100 already has.
Sending items of the LMD-100:
SV, Alarm 1 value, OUT1 proportional band, OUT2 proportional
band, Integral time, Derivative time, ARW, OUT1 proportional
cycle, OUT2 proportional cycle, Manual reset, Set value lock,
AT/Auto-reset
However, if SV is changed from the controller side, the SV of the
Set value memory number cannot be changed.
To change SV of the Set value memory number, set it in the next
“SV setting” mode.
• Setting range: 1 to 6
SV
CH
MEMO
PV
SV
• Sets the SV of the connected controllers and SV of the Set value
memory number selected during Set value memory number selection.
• Setting range: Scaling low limit to Scaling high limit
SV low limit to SV high limit
Alarm 1 value
CH
MEMO
PV
SV
• Sets the action point of Alarm 1 output of the connected controller.
Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)
• When No alarm action is selected for the controller, the SV display
is unlit, and this setting is impossible.
• Setting range depends on the alarm type of the connected controller.
OUT1 proportional band
CH
MEMO
PV
SV
• Sets OUT1 proportional band of the connected controllers.
OUT1 becomes ON/OFF action when set to 0 or 0.0.
• Setting range:
DCL-33A, JCL-33A, ACS-13A
: 0.0 to 110.0%
JCS-33A, JCM-33A, JCR-33A, JCD-33A: 0 to 1000
(2000 )
Thermocouple, RTD input with decimal point: 0.0 to 1000.0 ( )
DC voltage, current input: 0.0 to 100.0%