3.3 Panel Cutout

(Scale: mm)

Caution

If horizontal close mounting is used for the controller, IP66 specifications (Drip-proof/Dust-proof) may

be compromised, and all warranties will be invalidated.

Lateral close mounting

n: Number of units mounted

(Fig. 3.3-1)

3.4 Mounting to and Removal from the Control Panel

3.4.1 How to Mount the ACS-13A- /A

Mount the controller vertically to the flat, rigid panel to ensure it adheres to the Drip-proof/Dust-proof

specifications (IP66).

Mountable panel thickness: 1 to 5 mm

(1) Insert the controller from the front side of the panel. (Fig.3.4.1-1)

(2) Insert the mounting frame until it comes into contact with the panel, and fasten with screws.

Tighten screws with one rotation upon the screw tips touching the panel. (Fig.3.4.1-2)

The torque is 0.05 to 0.06 N•m.

3.4.2 How to Remove the Mounting Frame and Unit

(Fig. 3.4.2-1)

(1) Turn the power to the unit OFF, and disconnect all wires before removing the mounting frame.
(2) Insert a flat blade screwdriver between the mounting (screw) frame and unit

1

.

(3) Slowly push the frame upward using the screwdriver

2

, while pushing the unit toward the panel

3

.

(4) Repeat step (2) and slowly push the frame downward using the screwdriver for the other side.

The frame can be removed little by little by repeating these steps.

(Fig.3.4.1-1) Mounting

(Fig.3.4.1-2) Mounting

(Fig.3.4.2-1) Removal

4. Wiring

Warning

Turn the power supply to the instrument off before wiring or checking. Working on or touching the
terminal with the power switched on may result in severe injury or death due to electrical shock.

Caution

• The terminal block of this instrument is designed to be wired from the left side. The lead wire

must be inserted from the left side of the terminal, and fastened with the terminal screw.
The torque should be 0.63 N•m.

• This instrument does not have a built-in power switch, circuit breaker or fuse. It is necessary

to install a power switch, circuit breaker or fuse near the controller externally.

(Recommended fuse: Time-lag fuse, rated voltage 250 V AC, rated current 2 A)

• For a 24 V AC/DC power source, do not confuse polarity when using direct current (DC).
• For the input, use the infrared temperature sensor RD-500 series or RD-715-HA.
• When using a relay contact output type, externally use a relay according to the capacity of

the load.

• When wiring, keep input wires away from AC sources or load wires.

75

45

+0.5

0

45

+

0.

5

0

45

+

0.

5

0

n x 48-3

+0.5

0

Gasket

Mounting frame

Summary of Contents for ACS-13A-*A Series

Page 1: ...f life or damage occurring due to the instrument being used under conditions not otherwise stated in this manual Caution with Respect to Export Trade Control Ordinance To avoid this instrument from being used as a component in or as being utilized in the manufacture of weapons of mass destruction i e military applications military equipment etc please investigate the end users and the final use of...

Page 2: ...tely the following operations can be conducted from an external computer using the Console software SWS ACS01M 1 Reading and setting of SV PID various set values 2 Reading of PV and action status 3 Function change 3 Mounting to the Control Panel 3 1 Site Selection Caution Use within the following temperature and humidity ranges Temperature 0 to 50 32 to 122 Humidity 35 to 85 RH No icing and non co...

Page 3: ...nel 3 4 Repeat step 2 and slowly push the frame downward using the screwdriver for the other side The frame can be removed little by little by repeating these steps Fig 3 4 1 1 Mounting Fig 3 4 1 2 Mounting Fig 3 4 2 1 Removal 4 Wiring Warning Turn the power supply to the instrument off before wiring or checking Working on or touching the terminal with the power switched on may result in severe in...

Page 4: ...s numbered 7 to 12 into the holes of the terminal cover Fig 4 3 1 Solderless terminal Manufacturer Model Tightening torque Nichifu Terminal Industries CO LTD TMEV1 25Y 3 Y type Japan Solderless Terminal MFG CO LTD VD1 25 B3A Nichifu Terminal Industries CO LTD TMEV1 25 3 Ring type Japan Solderless Terminal MFG CO LTD V1 25 3 0 63 N m 4 4 Heater Burnout Alarm W W3 option Wiring This alarm is not usa...

Page 5: ... mode is changed it will affect other setting items such as the SV and Alarm value Infrared emissivity 0 200 to 1 000 Integral time 0 to 1000 sec Sensor correction 100 0 to 100 0 Infrared emissivity 2 0 200 to 1 000 Derivative time 0 to 300 sec Infrared emissivity 3 0 200 to 1 000 ARW 0 to 100 Communication protocol Shinko protocol Modbus ASCII Modbus RTU Infrared emissivity 4 0 200 to 1 000 OUT1 ...

Page 6: ... infrared ray is to be radiated the lower the emissivity value For objects such as organic substances or ceramics emissivity is so high that high accuracy measurement and control are possible On the contrary for the highly lustrous metals or other objects with low emissivity its emissivity is greatly affected by reflection In this case by attaching black body tape to the surface of those objects t...

Page 7: ...gh limit A M Alarm 1 delay time 0 to 10000 sec OUT1 ON OFF hysteresis 0 1 to 100 0 Alarm 2 delay time 0 to 10000 sec SV rise rate 0 0 to 1000 0 min min PV color Green Red Orange Alarm 1 or Alarm 2 ON Green Red Alarm 1 orAlarm 2 ON Orange Red PV continuous change PV continuous change Alarm 1 or Alarm 2 ON Red OUT2 cooling mode Air cooling Oil cooling Water cooling OUT2 high limit OUT2 low limit to ...

Page 8: ...o 28 V AC DC Accuracy Setting Indication Within 0 2 of temperature span 1 digit Control output OUT1 Relay contact 1a Control capacity 3 A 250 V AC resistive load 1 A 250 V AC inductive load cos 0 4 Electrical life 100 000 cycles Non contact voltage for SSR drive 12 V DC 15 Max 40 mA DC short circuit protected Direct current 4 to 20 mA DC Load resistance Max 550 Alarm 1 Alarm 2 A2 option Heater bur...

Reviews: