9. MAINTENANCE
VM-5S
-62-
9-2 VERIFICATION OF OK (INPUT ABNORMAL ALARM) OPERATION
This clause is used to test the display and contact output of OK (INPUT ABNORMAL ALARM).
•
Since OK (INPUT ABNORMAL ALARM) will be output during the test, open the
circuit between the alarm contacts and the connected system if necessary.
•
Set each Alarm Bypass Switch to “OFF” position.
• The machine is not protected during operation test.
9-2-1 INTERCONNECTION (ex. VM-5G SINGLE UNIT INSTRUMENT RACK)
Connect a input transducer to the input terminal of the VM-5G Single Unit Instrument Rack and
check the circuit of OK, ALERT contact points.
• Connect to the input/output terminals of the channel under operation test.
• Refer to “4. INTERCONNECTION” on page 4.