4. INSTALLATION
CV-86
-7-
4-4 CABLE
Observe the following notes for cabling.
(1) Use the CW-050 standard cable for connection with the CV-861 connector type version.
Use the twisted pair, shielded cable AWG No.16 to 20 (0.5mm
2
to 1.25mm
2
) for connection between the
junction terminal and monitoring device. Select suitable cable for operating environments.
(2) The cable should not exceed 300 meters. Excessive length may limit the systems frequency response.
(3) Keep cabling away from power and control lines, to prevent noise interference.
(4) Cable should be securely fixed. Prevent the cable from bending sharply, twisting, kinking,
knotting, and straining. The recommended minimum bend radius is 80mm. Refer to below drawing.
SHINKAWA recommends that the cable should be routed, through conduit to prevent physical damage
and noise interference.
! CAUTION
Beware not to apply the excessive force to the connector cable, which may cause the
damage.
Dimension : mm