3-4

Wiring

(1) Make sure that wiring operation is properly done in line with a terminal wire 
      diagram of section 3-5.
(2) Choose a suitable compensation lead wire in the case of thermocouple input.
(3) In the case of resistance bulb input, resistance value of each lead wire must be 
      less than 5Ω and that of three lead wires must be equal. 
(4) Do not wires an input signal line inside of an electric wire pipe or a duct same 
      with the high voltage line.
(5) Shield wiring (single point grounding) is effective against static induction noise.
(6) Wiring twisted at equal short intervals is effective against electromagnetic 
      induction noise.

3-2. Mounting

(1) Machine the mounting hole by referring to the panel-cut illustration in Section  
      3-3.
(2) Applicable thickness of the mounting panel is 1.2 ~ 2.8mm. 
(3) As this product provides mounting fixture, insert the product into the panel.

3-3. External dimension and panel cutout

MAC3 external dimensions (unit : mm)      

MAC3 panel cutout  (unit : mm)      

◎ 

Do not turn on electricity while wiring to avoid an electric shock.

◎ 

Do not touch a terminal or live part while turning on electricity.

Proximity attachment by a single hole is possible only in the case of 
horizontal direction.
When an apparatus that was attached in vertical direction is removed, 
a dedicated detachment tool is required.

NOTE

 : 

MAC3A

MAC3B

MAC3C

MAC3D

MAC3A

  

96×96size

MAC3B

  

48×96size

MAC3C

  

72×72size

In the case of horizontal proximity attachment by a single hole

N : Number

In the case of horizontal proximity attachment by a single hole

N : Number

In the case of horizontal proximity attachment by a single hole

N : Number

In the case of horizontal proximity attachment 
by a single hole

      

N : Number

MAC3D

  

48×48size

!

WARNING

(96

×

N−4)

96min

96min

92

+0.8 -0

+0.8

-0

+0.8

-0

+0.8 -0

92

92

48min

96min

+0.8 -0

+0.8 -0

+0.6

-0

+0.6

-0

45

92

92

(48

×

N−3)

72min

72min

+0.7

-0

68

+0.7 -0

68

+0.7 -0

68

+0.7

-0

(72

×

N−4)

48min

48min

+0.6

-0

45

+0.6 -0

45

+0.6 -0

45

+0.6

-0

(48

×

N−3)

96

69

66

69

96

48

96

72

72

48

48

4

4

4

4

4

66

Summary of Contents for MAC3 Series

Page 1: ...t 7 DI N none D external control input DI 1 2 3 three points 8 CT Input N none H CT Input two points 9 Analog Output N none T current 4 20mA V voltage 0 5V 10 Communication N none R RS485 11 Program F...

Page 2: ...dimension and panel cutout MAC3 external dimensions unit mm MAC3 panel cutout unit mm Do not turn on electricity while wiring to avoid an electric shock Do not touch a terminal or live part while turn...

Page 3: ...c screen then it jumps to the lead screen of Mode 1 Press key for three seconds on the lead screen of each Mode screens then it jumps to the basic screen Press key for three seconds on the lead screen...

Page 4: ...ol stop Output OFF 0 operation conduct of control operation Choose RUN by key Decide by key then Monitor LED s RUN lights up to start control operation Initial value stanby Initial value at the time o...

Page 5: ...lized when measuring range unit and scaling are changed Lower limit value of target value is set The operation mode of each deviation alarm is Effective at the time of automatic output Each deviation...

Page 6: ...peration or PI operation in D OFF setting The offset correction at the time of I OFF P operation PD operation is performed This screen is not displayed at the time of ON OFF operation The differential...

Page 7: ...1 standby operation setting screen Event 1 latching setting screen Event 1 output characteristics setting screen Event 2 mode setting screen Initial value 0 0 Setting range 0 0 99 9 Contents is the s...

Page 8: ...tion is possible no decimal pont 0 1 0 01 0 001 Unit Code Measureing Range Input Type Code Unit Code The same as event 1 Event 2 output characteristics setting screen Initial value Setting range The s...

Reviews: