CAUTION

For safety’s sake and to maintain the proper functioning of the 
product, you should not draw it out from its case. 
If it is necessary to draw out the instrument, contact our office in 
your neighborhood 

(1)  Machine the mounting hole by referring to the panel cutout 

drawings in Section 2-3. 

(2)  Applicable thickness of the mounting panel is from 1.0 to 4.0 

mm 

(3)  This product is provided with pawls which fix it when it is 

pressed straight into the front panel. 

ʹǦ͵Ǥ”ƒ™‹‰••Š‘™‹‰‡š–‡”ƒŽ†‹‡•‹‘•ƒ†’ƒ‡Ž…—–‘—–

(1)  SR82 

(2)  SR83 

(3)  SR84 

(4)  Current transformer (CT) for heater break alarm 

For 0-30 A (CTL-6-S) 

For 0-50 A (CTL -12-S36-8) 

ʹǦͶǤ‹”‹‰

(1)  Wiring should be carried out according to the drawings in "2-5. 

Terminal arrangement."  Confirm that there is no wrong 
connection 

(2)  Use crimp terminals which meet the M3.5 screw and are less than 

7 mm in width. 

(3)  For thermocouple input, select a compensation wire suitable for 

the particular type of thermocouple. 

(4)  For R.T.D. input, each lead should be less than 5

Ÿ

in resistance 

and three leads should have the same resistance. 

(5)  The input signal line should be conducted safely apart from high 

voltage power lines. 

(6)  Shield wiring (one-point grounding) works effectively against 

static induction noise. 

(7)  Twisting the input signal wire at equal intervals is effective 

against electromagnetic induction noise. 

(8)  For power lines, use wire or cable which is 1 mm

2

in size or 

thicker and is equivalent to or higher in grade than 600V vinyl 
insulated wire 

(9)  Earth wiring should be carried out with less than 100

Ÿ

 ground 

resistance by using wire which is 2 mm

2

or thicker. 

(10) Noise filter: If the instrument appears to be easily affected by 

power supply noise, use a noise filter for preventing malfunction. 
The noise filter should be mounted on the grounded panel and 
make wiring between the controller and the power terminal as 
short as possible. 

·

CAUTION

If the product is a thermocouple input specification, the cold junction is 
exposed at the terminal No. 6 (for SR82) or the terminal No. 8  
(for SR83/SR84)

Do not touch here with a screwdriver or anything when writing. 

·

WARNING

• The product must be disconnected from its power source 

during wiring operation so as to prevent electric shock. 

• The protective conductor (earth) terminal 

 must be grounded 

prior to use.  Otherwise, electric shock may result. 

• Do not touch the wired terminals and charged devices while 

power is on. 

Summary of Contents for SR80 Series

Page 1: ...f it goes out of the range a rise in temperature will reduce the product life and or result in problems with the product The output terminal should be connected with a device which meets IEC61010 requ...

Page 2: ...k alarm 50A 1 Remote input 2 00 None 14 4 20mA DC Not insulated 15 1 5V DC Not insulated 16 0 10V DC Not insulated Analog output 3 0 None 3 0 10mV DC 4 4 20mA DC 6 0 10V DC Communication 3 0 None 5 RS...

Page 3: ...high voltage power lines 6 Shield wiring one point grounding works effectively against static induction noise 7 Twisting the input signal wire at equal intervals is effective against electromagnetic i...

Page 4: ...ransformer CT Pass one load wire through the hole specifically provided or CT CT terminals on the secondary side are wired to the CT input terminal of the SR80 controller 1 SR82 2 SR83 1 Output 2 Outp...

Page 5: ...y parameter screen the mode 0 basic screen returns onto the display 2 parameter key When pressed on any of the mode 0 and 1 screen groups the next screen appears When this key is pressed continuously...

Page 6: ...digit digit digit digit digit digit...

Page 7: ...0 32 screens are the same as the other PID parameters Initial value 2 0 digit Setting range 1 1000 digit digit Initial value 2 0 digit Setting range 1 1000 digit Initial value 2 0 digit Setting range...

Page 8: ...digit digit It is conditional that rE_L rE_H It is conditional that rE_L rE_H...

Page 9: ......

Page 10: ...s effect when DI input turns ON When to detect external control input signal Level input The action is maintained as long as the contact remains ON Edge input The action is maintained even when the co...

Page 11: ...key for confirmation The AT lamp goes out Note When AT is cancelled in the mid operation PID values remain unchanged AT is automatically cancelled under the following conditions 1 Output value remains...

Page 12: ...STBY EXE 3 SV is changed where standby set value is a deviation value Except during remote input though When the standby action setting is changed to oFF or 4 while standby is in action the standby a...

Page 13: ...lamp display Control output OUT1 2 green Event action EV1 2 3 orange Auto tuning action AT green Manual control action MAN green Set value bias action SV2 SB green Remote action REM green Standby acti...

Page 14: ...ual switching Front key operation or DI external switching input through communication Manual control output 0 0 100 0 out of output limiter range possible Setting resolution 0 1 Manual automatic cont...

Page 15: ...1 RS 232C RS 485 Communication system RS 232C 3 line half duplex system RS 485 2 line half duplex multiple drop bus system Synchronization system Start stop synchronization system Communication distan...

Page 16: ...tween input output terminals and power terminal 500V DC 20M minimum Between input output terminals and protective conductor terminal 500V DC 20M minimum Dielectric strength 1 minute at 3000V AC betwee...

Reviews: