(4)  1-62 AT execution point setting screen 

For the purpose of avoiding hunting due to a limit cycle with a 
set SV AT execution, a virtual SV value (AT execution point) 
is set for AT to run at a point away from the actual SV value. 

Note 1: For AT execution point, an absolute value of difference 

between SV value and virtual SV value is to be input. 

Note 2: When 0 is set for AT execution point, SV value serves as 

the AT point. 

Note 3: When PV value is in the AT execution point area, SV value 

serves as the AT point.

ͷǤ—’’Ž‡‡–ƒ”›‘–‡•‘‡›‘’‡”ƒ–‹‘

ͷǦͳǤ

When AT is executed, PID constants are calculated and defined 
from repeated ON/OFF action (100%/0%) output for the 
measuring value increase and decrease around the set value and 
are stored in the internal memory to complete operation. Upon 
completion, control using stored PID constants begins. 

How to execute AT 

1. Press the 

 key in the mode 0 screen group.  Auto tuning is 

brought to the state of standby.  (AT lamp lights.) 

2. Press the 

 key to register. Auto tuning is executed.  (AT lamp 

flashes.) 

Note: AT can be executed even with remote SV. (The remote SV 

at the time when AT execution point is set is used in the 
execution.) 

Note: AT cannot be executed in the mode 1 screen group. 

 AT is not executed in the following conditions (When the 

 key 

is pressed, the AT lamp goes out.) 
1. During ramp control 
2. During manual operation 
3. In the state of STBY 
4.

oFF

 setting for proportional band (ON/OFF action) 

5. Selection of 2 or 3 on the keylock mode setting screen 
6. Scaleover of PV value (measured value) 

Cancellation of AT 

AT can be cancelled in mid-operation by pressing the 

 key 

again.  Press the 

 key for confirmation.  The AT lamp goes out. 

Note: When AT is cancelled in the mid-operation, PID values 

remain unchanged. 

 AT is automatically cancelled under the following conditions: 

1. Output value remains at 0% or 100% for two or more hours. 
2. Power supply is interrupted due to power failure or for other 

reason. 

3. Scaleover of PV (measured value) during AT execution. 
4. STBY is executed. 

ͷǦʹǤƒ—ƒŽƒ†Œ—•–‡–

On the 0-1 OUT1 control output value display screen and 0-2 
OUT2 control output value display screen, it is possible to change 
to the control output manual mode and to set a manual control 
output value. 

Change to manual control mode 

On a display screen of control output intended to be changed (0-1 
or 0-2), press the ENT   key for 3 seconds continuously.  The 
MAN lamp flashes and it is changed to the manual mode to allow 
you to set a control output value by means of the 

 or 

 key. 

Likewise, the manual control output mode is switched to the 
ordinary automatic mode by continuously switching the  

 key 

for 3 seconds. Then the MAN lamp goes out. 

 Rules applied to manual control 

1. Manual control action and output value are kept in memory 

even when power is turned OFF and is reapplied. 

2. When the measuring range is changed, the manual control mode 

is cancelled and replaced by automatic control mode. 

3. Upon switching auto to manual, balanceless and bumpless 

control is carried out.  If the measured value is out of the 
proportional band at the time of mode switching, however, 
balanceless and bumpless control is not performed. 

4. The control output range in the manual control mode is within a 

range defined by output limiter.  (When P=OFF or during 
ON/OFF action, control is carried out with lower limit 

 : % 

and higher limit 

 100.0%. 

Nevertheless, 100% output is displayed as follows on account of 
limited display space. 

Summary of Contents for SR80 Series

Page 1: ...f it goes out of the range a rise in temperature will reduce the product life and or result in problems with the product The output terminal should be connected with a device which meets IEC61010 requ...

Page 2: ...k alarm 50A 1 Remote input 2 00 None 14 4 20mA DC Not insulated 15 1 5V DC Not insulated 16 0 10V DC Not insulated Analog output 3 0 None 3 0 10mV DC 4 4 20mA DC 6 0 10V DC Communication 3 0 None 5 RS...

Page 3: ...high voltage power lines 6 Shield wiring one point grounding works effectively against static induction noise 7 Twisting the input signal wire at equal intervals is effective against electromagnetic i...

Page 4: ...ransformer CT Pass one load wire through the hole specifically provided or CT CT terminals on the secondary side are wired to the CT input terminal of the SR80 controller 1 SR82 2 SR83 1 Output 2 Outp...

Page 5: ...y parameter screen the mode 0 basic screen returns onto the display 2 parameter key When pressed on any of the mode 0 and 1 screen groups the next screen appears When this key is pressed continuously...

Page 6: ...digit digit digit digit digit digit...

Page 7: ...0 32 screens are the same as the other PID parameters Initial value 2 0 digit Setting range 1 1000 digit digit Initial value 2 0 digit Setting range 1 1000 digit Initial value 2 0 digit Setting range...

Page 8: ...digit digit It is conditional that rE_L rE_H It is conditional that rE_L rE_H...

Page 9: ......

Page 10: ...s effect when DI input turns ON When to detect external control input signal Level input The action is maintained as long as the contact remains ON Edge input The action is maintained even when the co...

Page 11: ...key for confirmation The AT lamp goes out Note When AT is cancelled in the mid operation PID values remain unchanged AT is automatically cancelled under the following conditions 1 Output value remains...

Page 12: ...STBY EXE 3 SV is changed where standby set value is a deviation value Except during remote input though When the standby action setting is changed to oFF or 4 while standby is in action the standby a...

Page 13: ...lamp display Control output OUT1 2 green Event action EV1 2 3 orange Auto tuning action AT green Manual control action MAN green Set value bias action SV2 SB green Remote action REM green Standby acti...

Page 14: ...ual switching Front key operation or DI external switching input through communication Manual control output 0 0 100 0 out of output limiter range possible Setting resolution 0 1 Manual automatic cont...

Page 15: ...1 RS 232C RS 485 Communication system RS 232C 3 line half duplex system RS 485 2 line half duplex multiple drop bus system Synchronization system Start stop synchronization system Communication distan...

Page 16: ...tween input output terminals and power terminal 500V DC 20M minimum Between input output terminals and protective conductor terminal 500V DC 20M minimum Dielectric strength 1 minute at 3000V AC betwee...

Reviews: