13 -

(3) Heater break alarm setting

The heater break alarm set screen is shown in case where heater break alarm option is added and heater break alarm of the alarm type select digit on

mode 2 screen is selected.

Displayed by pressing the 

key on higher limit alarm set screen, upper row shows the real time current value and lower row shows alarm action

current set value.

Break alarm value can be selected from OFF and range of 0.1~50.0A, heater break alarm is disabled by selecting OFF.

By setting OFF during heater break alarm signal output, heater break alarm output is terminated.

For set value other than OFF, heater break alarm signal is output if the current that flows in case where control output (contact or SSR drive voltage)

is ON, is less than set value.

If LOCK mode is selected at heater break alarm action mode select digit on mode 2 screen and the break alarm signal is output, alarm signal is only

terminated by changing the break alarm value into OFF or shutting down power.

If REAL mode is selected and heater current is less than current value being set, break alarm signal is generated. If heater current exceeds the

current threshold (0.1A), output of break alarm is terminated.

With the 

or 

key, value at which heater break alarm signal should be output is set and registered with 

key.

Example: In case of setting heater break alarm action point at 25.0A.

6. Supplement

6-1. Auto return function

When no key action is made for longer than three (3) minutes on each screen except heater break alarm value set screen, the screen moves back to the
basic screen of the mode 0 screen group (auto return).

6-2. PID (Screen No.2,4 and 5 of mode 1 screen group)

PID values are automatically set by performing auto tuning, modification may be required for object to be controlled.
If auto tuning is not performed, PID values should be set. Description for PID is as follows:

(1) P (proportional action)

Control output rate (%) is set for measuring range.
Control output value changes in proportion with measured value (PV) and set value (SV).
For wide proportional band, change of control output is small relative to deviation. The narrower the proportional band is, the larger the output
variation is and the more intense proportional action is. Too narrow proportional band causes ON-OFF like action with oscillation (hunting). By setting
P to be OFF, ON-OFF action is performed.

(2) I (integral time)

A function that compensates the offset created by proportional action. Effect of compensation is weaker for longer integral time and is intensified by
shortening time. Too short integral time causes integrating hunting and may result in wavy operation.

(3) D (derivative time)

Improves stability of control by reducing overshooting of integration from expected change of the control output. Effect of compensation is weaker for
shorter derivative time and is intensified for longer time. Too long derivative time may result in oscillating operation.

0-4 heater break alarm set screen

point flashing

point flashing

point goes off to
indicate registration

key

key

key

one by one

continuing

Summary of Contents for SR70 Series

Page 1: ...ties additional instructions are indicated by the following headings WARNING Exercise extreme caution as indicated This heading indicates hazardous conditions that could cause injury or death of perso...

Page 2: ...ge 23 The output terminal should be connected with a device which meets the requirements of IEC1010 A voltage current different from that of the input specification should not be added on the input te...

Page 3: ...resentative or our local office concerning any problems with the product accessories or related items 1 2 Caution for use 1 Avoid operating keys of the front panel with hard or sharp objects or motion...

Page 4: ...se and rotate the screwdriver while pushing up the lock lever behind the packing Once the instrument comes out by a few millimeters you can remove it by hand 2 4 External dimensions and panel cutout S...

Page 5: ...nal Recommendable noise filter TDK ZMB2203 13 Name of terminal and description Power terminal 100 240V AC 10 50 60Hz 11VA Protective conductor terminal Input terminal R T D A Thermocouple Voltage Curr...

Page 6: ...3 AH alarm output monitor LED red Turns on for higher limit alarm output ON 4 AL HB alarm output monitor LED red Turns on for lower alarm output ON or heater break alarm ON Key switches 1 parameter ke...

Page 7: ...econds on basic screen of the mode 0 screen group to change the screen into mode 2 screen Keep pressing key for five 5 seconds on the mode 2 screen to change screen into basic screen of the mode 0 scr...

Page 8: ...ssed the flashing decimal point in the rightmost digit moves from the top row bottom row top and bottom rows top row In case the lower limit value and the higher limit value are set to produce a diffe...

Page 9: ...action mode select digit Initial value Select from Lock mode and REAL mode Refer to 5 3 3 Input scaling screen Initial value Lower limit value top row 0 0 Higher limit value bottom row 100 0 Position...

Page 10: ...20 21 22 39 40 41 42 43 44 45 46 Measuring range F 0 3300 0 3100 0 3100 150 750 0 2200 0 1300 0 1100 300 400 0 2300 300 400 0 1100 300 1100 150 0 200 0 50 0 120 0 0 400 300 1100 150 0 200 0 50 0 120...

Page 11: ...in the following condition during AT execution Duration equal to or longer than 2 hours passed in the output level of 0 or 100 Power shutdown PV measured value is over the scale during AT execution 5...

Page 12: ...s selected Lower limit deviation value alarm is output for measured value to be less than set value alarm set value For lower limit deviation value alarm if set value alarm set value is less than the...

Page 13: ...ade for longer than three 3 minutes on each screen except heater break alarm value set screen the screen moves back to the basic screen of the mode 0 screen group auto return 6 2 PID Screen No 2 4 and...

Page 14: ...B and multiple break of A B B upon R T D input 2 Defect of heater break alarm CT CT input value is greater than 55A CT input value is less than 5A NOTE Message of heater break alarm is only displayed...

Page 15: ...C to the negative side of measuring range in case of T and U input though JIS Pt100 Jpt100 3 wire type Approx 0 25mA 5 max wire The 3 lead wires should have same resistance 0 10 10 50 0 100mV DC or 0...

Page 16: ...ge detected by externally attached CT Alarm output On upon detection of heater break while control output is On Off 0 1 50 0A Alarm action stops when Off is set 0 1A 0 0 55 0A 5 FS when sine wave is 5...

Reviews: