- 23 - 

6 Operation and Functions 

6-1. Using FIX Mode 

FIX: Adjustment function without using the program function. 

  Pressing the 

  or 

  key on the 3-1 FIX ON/OFF screen turns OFF shown on the target value (SV) display to ON and the decimal point of the 

rightmost digit blinks. Then, press the 

  ENT key, and the decimal point stops blinking to register the selection. (When OFF is set for FIX on this 

screen, the program mode turns ON.) 

  Pressing the 

  key calls the next setting screen. Set a necessary item, if any. 

  When the display returns to the basic screen upon completion of setting,    is shown on the pattern number display and the FIX mode is ON. 

6-2. Setting Target Value (SV) (FIX Mode) 

  Setting on the basic screen 

When the 

  or 

  key is pressed on the 0-0 basic screen, the decimal point of the rightmost digit blinks and the numerical value changes. The value 

keeps changing while either of the keys is being pressed. Once an intended value is reached, press the ENT key to register it. The registration of the data 
stops the blink of the decimal point. 

  Setting on the SV setting screen 

When the 

  or 

  key is pressed on the 3-2 FIX SV setting screen, the decimal point of the rightmost digit blinks and the numerical value changes. 

The value keeps changing while either of the keys is being pressed. Once an intended value is reached, press the 

  key to register it. The registration of 

the data stops the blink of the decimal point. 
* In the program mode, SV value is unable to be changed on the basic screen. 
* In the program mode, the 1-1 start SV setting screen and the 2-1 step SV setting screen should be used to set an SV. 
* No target value can be changed while auto tuning (AT) is in execution. It should be set after releasing AT. 

6-3. Setting Output Manually 

For switching between auto and manual, press the 

  key continuously for 3 seconds (in the state of RUN) on the output monitoring screen. 

During manual output, the MAN lamp lights and it goes out when automatic output begins. 
To set a target value, press the 

  or 

  key on the output monitoring screen. When the target value is reached, the setting completes. To release it, press 

the 

  key again for 3 seconds continuously, and automatic output is resumed. 

* Changing to manual output is not possible while auto tuning is in execution. 

  100% output is shown as 

  and the decimal point of    blinks. 

  When OFF is set for proportional band (P) in the case of contact output or SSR drive voltage output, the value of output is either 0.0% or 100.0%. 
  When OFF is set for proportional band (P) in the case of voltage output or current output, the output value becomes the lower or higher limit value of a set 

output limiter. 

  Supplementary Explanation of Monitoring Screen 

The output monitoring screen (OUT) and automatic output/manual output: 
1) When auto is changed to manual, output is in balanceless action and an output value immediately before the change is displayed. When manual is changed to 

auto, output is in bumpless action if it is bumpless. If it is outside the proportional band, however, the output is not in bumpless action. 

2) In case power supply was turned OFF and power is applied again, control output is in the mode (either manual or auto) which was ON at the time of 

interruption of power supply. 

NOTE: Even in the manual mode, it is possible to call another screen but it should be noted that control output is in the manual state. Blinking of the MAN 

action LED shows that the manual mode is ON. 

6.4. Auto Tuning (AT) 

This is the function to automatically calculate and set P.I.D. values, i.e., parameters of PID control. The time required for calculation depends on the details of 
control. 

 Execution of AT 

Pressing the 

  key on the AT execution setting screen changes OFF shown on the target set value (SV) display to ON and the decimal point on the 

rightmost digit blinks. Upon pressing the 

  key, the decimal point stops blinking and AT action begins. When the target set value stays in the inclined 

portions (portions indicated by the arrows of the action display), AT is in the state of standby (the AT lamp lights), and AT is executed while the target set 
value stays in the level portion (the AT lamp blinks). 
While AT is in execution, the ON/OFF action of output is repeated several times in accordance with rise and fall of the measured value from the target 
value as the border and PID values are stored in an internal memory. Immediately when they are stored, control using these PID values begins and AT 
action ends. Then, the target set value display shows OFF and the AT lamp goes out. (In case there is AT still to be executed, it is put in the state of 
standby.) 

Summary of Contents for FP93

Page 1: ...otice Please ensure that this instruction manual is given to the final user of the instrument Preface This instruction manual is meant for those who will be involved in the wiring installation operati...

Page 2: ...Setting Step SV 17 2 Setting Step Time 17 3 Setting PID No 17 5 8 Explanation of screen Group 3 and Setting 17 1 Setting ON OFF of FIX Mode 17 2 Setting FIX SV Value 17 3 Setting FIX No 17 4 Setting F...

Page 3: ...the switch or the breaker adjacently to the instrument in a position which allows it to be operated with ease with an indication that it is a means of turning the power off Use a switch or a breaker...

Page 4: ...resistor 250 for current input 1 pc Terminal resistor 120 for RS 485 1 pc NOTE For any problem with the product shortage of accessories or request for information please contact our sales agent 2 2 Ha...

Page 5: ...ction 3 5 and the terminal arrangement in Section 3 6 and make sure to carry out the correct wiring d Use press fit terminal which fits an M3 5 screw and has a width of 7 mm or less e In case of therm...

Page 6: ...output Contact COM SSR drive voltage Voltage Current Contact NO SSR drive voltage Voltage Current Contact NC 14 15 16 Event output COM EV1 EV2 EV3 17 18 19 20 Analog output option 21 22 Communication...

Page 7: ...ed as communication mode 9 AT green Auto tuning action lamp Blinks while AT is in execution The lamp lights during standby for AT and goes out when AT action comes to an end or is terminated 10 MAN gr...

Page 8: ...essed in the middle of setting in screen groups 1 3 4 or 5 the initial screen of the group is called onto display When pressed in the screen group 2 the initial screen of screen group 1 is called onto...

Page 9: ...oup 5 calls the basic screen of screen group 0 NOTE 3 Pressing the key in any screen group calls the next screen and pressing it on the last screen of a screen group calls the initial screen NOTE 4 A...

Page 10: ...10...

Page 11: ...11...

Page 12: ...ting 5 32 Analog output type setting 5 11 PV filter setting 5 33 Analog output scaling lower limit setting 5 12 Output control characteristics setting 5 34 Analog output scaling higher limit setting 5...

Page 13: ...group 4 calls the basic screen of screen group 0 Pressing the key on the initial screen of screen group 5 calls the basic screen of screen group 0 Pressing the key on any screen midway of screen grou...

Page 14: ...g range codes on the 5 5 Measuring range code setting screen For current voltage or mV input lower higher limit values and the position of decimal point of the contents of display in response to input...

Page 15: ...PROG mode If stop RST is input through external control input DI 1 or in the case of a change to FIX mode through DI the 0 0 basic screen is returned In case is set for external control input DI it f...

Page 16: ...F Setting range OFF 1 End step A step in which TS2 signal is stopped is set This screen is not displayed when TS2 ON step is OFF A change of end step makes four decimal places blink if set value of en...

Page 17: ...out as PID No 1 To 2 1 screen 5 8 Explanation of screen Group 3 and Setting 3 0 Initial screen To 4 0 screen representing FIX mode is shown on PTN display 1 Setting ON OFF of FIX Mode 3 1 FIX mode ON...

Page 18: ...PID does not function and ordinary PID action is carried out This screen is not displayed when P OFF 4 7 Lower limit output limiter setting screen To 4 1 PID No 1 screen To 4 10 zone PID screen Initia...

Page 19: ...it of measuring range is displayed and no change is possible A set value is unable to be changed during RUN in the PROG mode To 5 8 screen 5 8 Input scaling higher limit value setting screen To 5 0 sc...

Page 20: ...5 19 Event 1 EV1 type setting screen To 5 0 screen Initial value Setting range The type of event to be set as EV1 is selected from the following table To 5 20 screen Table of Event Type Codes Code Typ...

Page 21: ...n To 5 0 screen Initial value The higher limit value of setting range for PV and SV and 100 0 for OUT Setting range Within measuring range when PV or SV is selected and 0 0 100 0 when OUT is selected...

Page 22: ...M LOC COM LOC Keyoperation Available Available Notavailable Available Communicationwriting Available Available Available Notavailable 18 Setting Keylock 5 45 Keylock setting screen To 5 0 screen Initi...

Page 23: ...o manual output is not possible while auto tuning is in execution 100 output is shown as and the decimal point of blinks When OFF is set for proportional band P in the case of contact output or SSR dr...

Page 24: ...unction to correct an offset constant deviation produced in proportional band The longer the integral time the weaker the correcting action that is reducing the integral time strengthens the correctin...

Page 25: ...by shorting across terminals 1 and 2 ADV As on the 0 6 ADV execution screen when executed the present step comes to an end and is forced to proceed to the next step Being edge input ADV is executed ev...

Page 26: ...g screen When event output is used as an alarm select from 1 2 and 3 of the standby action code table When event output is used for control set 4 control mode In case 4 is selected however event outpu...

Page 27: ...HLD the change is not reflected until HLD is released Reasons why time signal does not function always OFF Time signal does not function in the following cases 1 or is not set as status output of eve...

Page 28: ...r Break of thermocouple input wiring Break of R T D input A wiring Input measured value exceeded higher limit of measuring range by more than 10 Check thermocouple input wiring If wiring has no proble...

Page 29: ...alue includes action type E1 i Hd 2000 digit Ld 1999 digit od 2000 digit id 2000 digit HA Higher limit of measuring range LA Lower limit of measuring range 1 12 EV2 level value includes action type E2...

Page 30: ...ID hysteresis dF 20 digit 4 3 PID I I ijh 4 4 PID D d kh 4 5 PID MR mr rh 4 6 PID SF SF rlh 4 7 PID lower limit o_L rh 4 8 PID higher limit o_H ihrh PID No 5 4 0 Initial screen Pid 4 1 PID P P uh 4 2...

Page 31: ...External control input 4 code di4c l 5 19 EV1 action type E1_m i 5 20 EV1 hysteresis E1_d i 5 digit 5 21 EV1 standby setting E1_i i i 5 22 EV2 action type E2_m j 5 23 EV2 hysteresis E2_d j 5 digit 5...

Page 32: ...setting EV3 setting 20 The number of pattern executions 10 Guarantee soak PV start 0 Step No 1 2 3 4 5 6 7 8 9 10 SV set value Time PID No 0 6 Copy these pages for your use as occasion demands Zone PI...

Page 33: ...rent mA Thermocouple Input impedance 500 k minimum External resistance tolerance 100 maximum Influence of lead wire tolerance 1 2 V 10 Burnout function standard up scale Cold junction compensation acc...

Page 34: ...igits Within higher lower limit deviations 0 2000 digits Standby action Selectable from the following 4 types respectively for EV1 EV2 and EV3 None Standby 1 standby only when power is applied Standby...

Page 35: ...nd PID No Time signal 2 outputs pattern to be set within time setting range Number of pattern executions Maximum 9999 PV start ON OFF Guarantee soak OFF 1 999 digits Hold Front key input or external c...

Page 36: ...36 PRINTED IN JAPAN...